DIP switch 1-5:
OFF: Operator´s panel stop activated
ON:
Operator´s panel stop deactivated
To be switched ON in case the stop function
should be deactivated from the operator´s panel
DIP switch 1-6:
OFF: External stop deactivated
ON:
External stop activated
To be switched ON in case external stop function
should be activated via terminal X4.3 and X4.4
DIP switch 1-7:
OFF: Operator´s panel +/- activated
ON:
Operator´s panel +/- deactivated
To be switched ON in case the blowers output
adjustment should be deactivated from the
operator´s panel
All manuals and user guides at all-guides.com
DIP switch 1-8:
OFF: +/- input from operator´s panel
ON:
+/- input from PLC
To be put ON in case +/- should be controlled
from external PLC via terminal X6.1 and X6.2
DIP switch 2-1:
OFF: Active pressure transmitter via hardware (to be
connected to terminal X5.1 and X5.3)
ON:
Inactive pressure transmitter via Kongskilde
transmitter (to be connected to terminal X5.3 and
X5.4)
To be switched ON in case the blowers output
should be controlled by an inactive pressure
transmitter, connected to terminal X5.3 and X5.4.
To be switched OFF in case the output should
be controlled by an active pressure transmitter,
connected to terminal X5.1 and X5.3 (refer to the
electrical schematics).
Provides DIP switch 2-2 is ON
17