Descargar Imprimir esta página

Vortice VORT HR 300 NETI Manual De Instrucciones página 45

Ocultar thumbs Ver también para VORT HR 300 NETI:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 122
8.1 User Mode
Key A: Mode selection
Press key A to select the mode [press the key in sequence to cycle through the modes: Holiday mode, Min. mode, Med.
mode, OFF (if pressed for 5 seconds).
Holiday
LED 1 switches on, the fans run at a speed 30% lower than the minimum.
n this mode, boost is deactivated and bypass closed.
Min
LED 2 switches on, the fans run at minimum speed.
Med
LED 3 switches on, the fans run at medium speed: Vmed = (Vmin+Vmax) / 2
OFF
Press key A for 5 seconds to go to OFF mode, for more informations see page 33 "POST-VENTILATION" operation
Key B: Vmax mode
LED 4 switches on, the fans run at Maximum Vmax speed.
By pressing the button a second time the machine will return to the previously set speed.
Note: The key is disabled during Holiday mode.
Key C: Alarm reset
Here is how to distinguish and reset the various types of alarm:
• No alarm active: LED 6 off
• Non-locking clogged filter alarm: 6 slow flashing (0.5sec ON, 4sec OFF) Reset ONLY after filters have been changed (
tochange filter see section "Maintenance and Cleaning"). Hold down the C button for 5 seconds to reset it.
• Non-locking general alarm: 6 fast flashing (0.5sec ON, 0.5sec OFF) Press button C once to reset it, if the LED continues
to flash after pressing it, call the authorized VORTICE Technical Assistance Center.
• General blocking alarm: 6 on steady, NOT resettable, if it persists for more than 2 hours call the VORTICE authorized
technical assistance center.
8.2 Installer mode
The installer can adjust the minimum and maximum speeds independently before the supply motor and then for the exhaust
motor or set the default speeds.
The installer can enter into this operating mode by simultaneously pressing keys A and B for 5 seconds. All the LEDs will
flash 3 times and then switch off.
The supply fan will switch on at minimum speed while the exhaust fan will switch off. LEDs 6 and 2 will flash to indicate
"minimum supply speed" installation mode.
Key A: Installation mode selection
Repeatedly press key A in installer mode to select the minimum and maximum speed of the respective supply and
exhaust fans, in the following order: Vmin supply (LED 6 and LED 2 flashing) -> Vmin exhaust (LED 5 and LED 2 flashing)
-> Vmax supply (LED 6 and LED 4 flashing) -> Vmax exhaust (LED 5 and LED 4 flashing) -> all the LEDs will flash 3 times
and then will subsequently exit from installer mode.
Key B: increase speed +
The sole function of this key is to increase the current speed selected with key A.
• Repeatedly press to increase the speed by 1 unit
Key C: decrease speed -
The key has two functions: to decrease current selected speed by means of key A and, if pressed for 5 seconds, to restore
default speed values
• Repeatedly press to decrease the speed by 1 unit
Default values:
Minimum speed %
Exh/Sup
28/28
Maximum speed %
Exh/Sup
100/100
Medium speed %=> calculated %
Exh/Sup
64/64
ENGLISH
45

Publicidad

loading

Este manual también es adecuado para:

Vort hr 300 neti h1093010912