OUTDOOR UNIT INSTALLATION 
Step6: Vacuum Pumping 
6.1 Use a spanner to take down the protective caps from the service port, low pressure valve and 
high pressure valve of the outdoor unit. 
6.2 Connect the pressure hose of manifold gauge to the service port on the outdoor unit low 
pressure valve. 
6.3 Connect the charge hose from the manifold gauge to the vacuum pump. 
6.4 Open the low pressure valve of the manifold gauge and close the high pressure valve. 
6.5 Turn on the vacuum pump to vacuum the system. 
6.6
The vacuum time should not be less than 15 minutes, or make sure the compound gauge 
indicates ‐0.1 MPa (‐76 cmHg) 
6.7 Close the low pressure valve of the manifold gauge and turn off the vacuum. 
6.8 Hold the pressure for 5 minutes, make sure that the rebound of compound gauge pointer does 
not exceed 0.005 MPa. 
6.9 Open the low pressure valve counterclockwise for 1/4 turn with hexagonal wrench to let a little 
refrigerant fill in the system, and close the low pressure valve after 5 seconds and quickly remove 
the pressure hose. 
6.10 Check all indoor and outdoor joints for leakage with soapy water or leak detector. 
6.11 Fully open the low pressure valve and high pressure valve of the outdoor unit with hexagonal 
wrench. 
6.12 Reinstall the protective caps of the service port, low pressure valve and high pressure valve of 
the outdoor unit. 
6.13 Reinstall the valve cover. 
compound gauge 
Low pressure valve 
Service port 
High pressure valve 
Valve protective caps 
Pressure hose 
Manifold gauge 
Vacuum pump 
35 
EN - 30
Pressure gauge 
High pressure valve 
Low pressure valve 
Charge hose 