5.2.3 Control Type V V W (P202 = 5)

Seq
Display Indication/Action
1
Initialization mode
Press key
to enter the first level of the parameterization
mode
3
Press key
to change the content of "P202 - Type of
Control" for P202 = 5 (V V W ). Use key
5
If necessary, change the content of "P399 - Motor Rated
Efficiency" according to the nameplate
Press key
for the next parameter
7
If necessary, change the content of "P401 - Motor Rated
Current"
Press key
for the next parameter
9
If necessary, change the content of "P403 - Motor Rated
Frequency"
Press key
for the next parameter
11
If necessary, change the content of "P407 - Motor Rated
Power factor"
Press key
for the next parameter
13
During the self-tuning, the HMI will show "Auto", and the
bar will indicate the operation progress
15
If necessary, change the content of "P409 - Stator
Resistance"
First Time Power-UP and Start-UP
Seq
2
Press keys
4
Press key
Use key
6
If necessary, change the content of "P400 - Motor Rated
Voltage"
Press key
8
If necessary, change the content of "P402 - Motor Rated
Speed"
Press key
10
If necessary, change the content of "P404 - Motor Rated
Power"
Press key
12
If necessary to make the self-tuning, change the value of
P408 to "I"
14
When the self-tuning is completed, it will return to the (comp)
Initialization Mode
Figure 5.4: Sequence for VVW control
Display Indication/Action
or
to select parameter P296
to save the change of P202
to select parameter P399
for the next parameter
for the next parameter
for the next parameter
CFW100 G2 | 25