Vortice VORT HRI 200 PHANTOM BP IoT Manual De Instrucciones página 34

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

ITALIANO
11 Modbus
BMS
Modbus
index
address
1
0
3
2
5
4
7
6
8
7
air temperature (T2)
9
8
10
9
air temperature (T4)
18
17
23
22
49
48
50
49
51
50
55
54
56
55
57
56
75
74
34
Signal
Description
type
Program series
Status of work
Speed
I/O
Supply air
temperature (T1)
Extraction
Intake / exhaust air
temperature (T3)
Exhausted
Bypass
actuator state
Pre-heater (N1)
Speed W1 in run 1
I/O
Speed W1 in run 2
I/O
Speed W1 in run 3
I/O
Speed W2 in run 1
I/O
Speed W2 in run 2
I/O
Speed W2 in run 3
I/O
Device address
for BMS
communication
Value
Value
Min.
Max.
O
0
0xFFF
O
0
1
0
6
O
-40,0
60,0
O
-40,0
60,0
O
-40,0
60,0
O
-40,0
60,0
O
0
1
O
0
1
dyn. (15) dyn. (100)
dyn. (15) dyn. (100)
dyn. (15) dyn. (100)
dyn. (15) dyn. (100)
dyn. (15) dyn. (100)
dyn. (15) dyn. (100)
O
0
247
Variable
Comments
type
Format: SXXX.YYY
hex
XXX - older byte
YYY - younger byte
integer
0 - Speed 0,
3 - Speed 1,
integer
4 - Speed 2,
5 - Speed 3.
999 - if sensor
integer
failure
999 - if sensor
integer
failure
999 - if sensor
integer
failure
999 - if sensor
integer
failure
0 - flow off,
integer
1 - flow on
0 - inactive,
integer
1 - active
integer
Control in %
integer
Control in %
integer
Control in %
integer
Control in %
integer
Control in %
integer
Control in %
integer

Publicidad

loading

Este manual también es adecuado para:

Vort hri 200 phantom bp iot hVort hri 350 phantom bp iot