Descargar Imprimir esta página

Mitsubishi Electric Mr.SLIM PUZ-ZM YKA2 Serie Manual De Instalación página 13

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 79
4. Installing the refrigerant piping
D
A
A Cover panel front
B Cover panel rear
C Stop valve
D Service panel
E Bend radius : 100 mm -150 mm
Fig. 4-4
4.3. Refrigerant piping (Fig. 4-4)
Remove the service panel D (3 screws) and the cover panel front A (2 screws) and
cover panel rear B (4 screws).
1 Perform refrigerant piping connections for the indoor/outdoor unit when the out-
door unit's stop valve is completely closed.
2 Vacuum-purge air from the indoor unit and the connection piping.
3 After connecting the refrigerant pipes, check the connected pipes and the indoor
unit for gas leaks. (Refer to 4.4. Refrigerant pipe airtight testing method)
4 A high-performance vacuum pump is used at the stop valve service port to main-
tain a vacuum for an adequate time (at least one hour after reaching –101 kPa (5
Torr)) in order to vacuum dry the inside of the pipes. Always check the degree of
C
vacuum at the gauge manifold. If there is any moisture left in the pipe, the degree
of vacuum is sometimes not reached with short-time vacuum application.
After vacuum drying, completely open the stop valves (both liquid and gas) for the
outdoor unit. This completely links the indoor and outdoor refrigerant circuits.
• If the vacuum drying is inadequate, air and water vapor remain in the refriger-
B
• If the stop valves are left closed and the unit is operated, the compressor and
• Use a leak detector or soapy water to check for gas leaks at the pipe connec-
• Do not use the refrigerant from the unit to purge air from the refrigerant lines.
• After the valve work is completed, tighten the valve caps to the correct torque:
5 Use sealant to seal the ends of the thermal insulation around the pipe connection
sections to prevent water from entering the thermal insulation.
ant circuits and can cause abnormal rise of high pressure, abnormal drop of
low pressure, deterioration of the refrigerating machine oil due to moisture, etc.
control valves will be damaged.
tion sections of the outdoor unit.
20 to 25 N·m (200 to 250 kgf·cm).
Failure to replace and tighten the caps may result in refrigerant leakage. In
addition, do not damage the insides of the valve caps as they act as a seal to
prevent refrigerant leakage.
en
11

Publicidad

loading