Descargar Imprimir esta página

STEINEL PROFESSIONAL HF 180 Manual página 15

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 35
DIP 2 – (AUTO�/MAN) fully automatic mode / semi-automatic mode
(Fig� 5�4)
Fully automatic mode: (AUTO)
Depending on brightness, the light switches on automatically if movement is
detected and switches off when the brightness increases or upon expiry of the
stay-ON time. The light can be switched ON and OFF manually at any time.
This temporarily interrupts the automatic switching function.
Semi-automatic mode: (MAN)
The light only switches OFF automatically. Light is switched ON manually,
request light via the switch. It remains ON for the stay-ON time selected.
DIP 3 – (used
/ not used
Selecting the "used" setting activates the integrated switch (A) as well as any
switch optionally connected to the S input. Set to "not used", the integrated
switch (A) and any switch optionally connected to the S input is deactivated
and therefore has no function.
The switch also influences interconnection with the P conductor.
(➜ "4� Electrical connection")
DIP 4 – (ON
/ ON/OFF
) (Fig� 5�4)
In the ON-OFF setting, the light can be switched ON and OFF manually at any
time (except in pulse mode: no manual OFF). In the ON setting, light can no
longer be switched OFF manually. The stay-ON time starts from the beginning
again each time the switch is pressed.
Switch for light function
The function of the integrated switch (A) depends on sensor configuration as
well as the current operating situation.
➜ "Light function" table
) (Fig� 5�4)
- 28 -
Twilight setting
Examples of use
Twilight operation
Corridors, foyers
Stairs, escalators, moving walkways
Washrooms, toilets, switch rooms, canteens
Sales floor, kindergartens, nursery school rooms,
sports halls
Work rooms: offices, conference and meeting rooms,
precision assembly activities, kitchens
Working areas requiring good light: laboratory,
technical drawing, precision work
Daylight operation
Note: Depending on the mounting location, this setting may need correcting.
The light level is measured at the sensor.
Light function
DIP switch 2
Switch configura-
mode
tion DIP switch 4
Fully automatic
ON / ON-OFF
mode
Fully automatic
ON-OFF
mode
Fully automatic
ON
mode
Semi-automatic
ON / ON-OFF
mode
Semi-automatic
ON-OFF
mode
Semi-automatic
ON
mode
Light-level settings
min
1
2
3
4
5
>=6
max
Status
Switch function
Lighting is
Lighting is switched
switched OFF
ON for the stay-ON
time selected
Lighting is
Lighting is switched
switched ON
OFF for the stay-ON
time selected and
re-triggered on
detecting movement
(inverse mode /
presentation mode)
Lighting is
The stay-ON time se-
switched ON
lected is re-triggered.
Lighting is
Lighting is switched
switched OFF
ON for the stay-ON
time selected.
Lighting is
Lighting is switched
switched ON
OFF until it is next
activated.
Lighting is
The stay-ON time
switched ON
selected is re-trig-
gered.
- 29 -

Publicidad

loading

Este manual también es adecuado para:

Ir 180