1. Install the power pack according to its instructions.
2. Connect the power pack wires to the sensor as follows:
RED wire (+24VDC) to the +24V IN terminal on the sensor.
BLACK wire (Return) to common (COMM.) terminal on the sensor.
BLUE wire to control output (CTRL. OUT) terminal on the sensor.
3. Wire the Isolated Relay. The Isolated Relay is rated for 1A @ 30VAC/VDC.
Connect the wires necessary to the application that requires this output:
• Normally Closed (N.C.) - Open when occupancy is detected.
• Relay Common (must be used for proper operation)
• Normally Open (N.O.) - Closed when occupancy is detected.
The bottom terminal on the sensor is not used.
NOTE: The isolated relay follows the actual occupancy state of the sensor
and is not affected by the switch.
4. Encienda la alimentación.
5. Pruebe y ajuste el sensor si es necesario.
6. Instale la placa de cubierta del interruptor de pared del decorador estándar de
la industria (no incluida).
1 2
Time Delay
Test/20 min
ON
5 minutes
15 minutes
30 minutes
Walk-Through
3
Walk-Through
Enabled
Trigger
Disabled
Mode
Standard
4
PIR Sensitivty
Option A
Low, 50%
Option B
High
Option C
Sensor Adjustment
Remove the wall plate. Remove the button cap by firmly squeezing together the top sides of the button assembly. Gently pull it away
from the unit.
When the adjustments are completed, replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the
top of the button while pressing it into the unit. Reinstall the cover plate.
Light Level Adjustment
The light level can be set with loads ON or OFF. To enable light level control and set the threshold:
1. Make sure the room is lit appropriately.
2. Put the sensor into TEST mode. You have 5 minutes to complete the procedure.
3. Press and hold the ON/OFF button for 3 seconds, until you hear a beep.
4. Step away from the sensor. After 25 seconds a beep sounds, indicating that the threshold level is set. This threshold is retained,
even if power is lost, until it is re-set or disabled.
To disable light level control, press and hold the ON/OFF button for 7 seconds, until a double beep tone sounds.
DIP SWITCH SETTINGS
ON Mode
Time
Trigger
Not Used
Delay
Mode
Audible Alert
1
2
3
4
5
6
7
8
9
Enabled
Disabled
Audible Alerts
PIR Sensitivity
ON Mode
Manual On
5 6
Auto On
Both
Either
Either
PIR
Either Either
Switch 9 is not used
PIR
PIR
PIR
=ON
Both
Both
Both
=Factory Setting
INSTALLATION
ON/OFF
Button
7
8
Tabs
Button
Hinges
=OFF
ADJUSTMENTS
3
WARNING: TURN THE POWER OFF AT
THE CIRCUIT BREAKER BEFORE WIRING.
White (Neutral)
Red (Line)
White
Power
Neutral
Pack
Black
Hot
+24 VDC
Common
Control Outputs
Normally closed contact
Common
Normally open contact
Not used
Lighting
Load
Red
(Load)
Isolated Relay Outputs
Ultrasonic Sensitivity
Adjustment Trimpot
DIP Switches
Ultrasonic Cones
Detection LEDs
Red = PIR
Green = Ultrasonic
PIR Lens

Publicidad