AF200E
8. Apéndices
8.1 - ELI02 Controller & Electrical Wiring Schematic
Drawing
A. PANEL CONTROLS DESCRIPTION
1. Main switch - Marked [ MAIN ]
Enable Connection of the LINE voltage supply to the control unit,
At this state green lamp indicator [ ON ] will lit.
2. Lamp indicator (Green) - Marked [ ON ]
Indicates 24Vac internal supply.
3. Lamp indicator (Red) - Marked [ FAULT ]
Indicates MOTOR over load failure. (Flushing disabled!)
4. Lighted Push-button switch (Orange) - Marked [ FLUSH ]
Enable filter manual FLUSH operation.
B. INTERNAL CONTROLS DESCRIPTION
1. OL , Motor over load protection 0.63-1amp. with aux. contacts.
2. e1 , 1 amp. Line protectors that serve as a main protect for the control unit.
3. e2 , 2 amp. Line protector which serve as a 24Vac protect for the control unit.
4. C1 , power relay which controls filter motor.
5. TR1 , Multi voltage / 24Vac transformer.
6. TP , Sets Differential pressure switch sense time.
7. TF , Sets the flushing time.
8. TD , Sets the interval time between flushes.
C. TERMINAL CONNECTIONS
1. TB 1-4
: Line supply 380-480Vac+GND,3 phase,50-60Hz. inlets.
2. TB 5-8
: 380-480Vac+GND,3 phase,50-60Hz. M1 - motor supply voltage outlets.
3. TB 9/10 : SV , Flushing solenoid outlets. (24V/10W COIL)
4. TB 11/12 : DP , Differential pressure switch inlets.
5. TB 13/14 : SET inlets , enable/disable interval timer TD.
D. INSTALLATION
General – The control unit & Filter junction box are supplied with 5 meters cable in
flexible conduit. The user should connect only the line supply cable through 11 mm
flexible conduit.
Paragraph 2 & 3 are for user knowledge in case of cables extension or rewiring.
33