Descargar Imprimir esta página

AERMEC MODUCONTROL Manual De Uso página 39

Regulación electrónica
Ocultar thumbs Ver también para MODUCONTROL:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Index - String
MIN value
-20 °C
1 StF
Index - String
MIN value
1 °C
2 bnF
Index - String
MIN value
3 StC
25 °C
Index - String
MIN value
4 bnC
1 °C
Index
MIN value
MAX value
- String
0
3
5 CSt
Cooling mode
Heating mode range
Setting of cooling temperature
MAX value
26 °C
This parameter indicates the value of the work setting active in cooling mode.
Setting of proportional cooling band
MAX value
This parameter indicates the proportional band applied to the cooling set; this band produces the optimised manage-
ment of the compressor, only switching it on if the inlet/outlet water temperature (depending on the type of control
20 °C
set by parameter (0) in the installer menu) is greater than the cooling work set (parameter (1) user menu) plus the
value of this parameter.
Setting heating mode temperature set
MAX value
This parameter indicates the active work set value in the heating mode. This parameter is displayed in the cooling only
units but cannot be modified.
(*):
(*)
- the maximum limit can be configured via the parameter (t) of the installer menu;
- if the parameter (8) of the installer menu is set at 4, the maximum limit becomes 70°C in order to allow insertion of a
set-point for boiler adjustment;
Setting of proportional heating band
MAX value
This parameter indicates the proportional band applied to the heating set; this band produces the optimised manage-
ment of the compressor, only switching it on if the inlet/outlet water temperature (depending on the type of control
20 °C
set by parameter (0) in the installer menu) is less than the heating work set (parameter (3) user menu), minus the value
of this parameter. In cooling only units, this parameter is displayed but it cannot be modified.
Settings made on the basis of outside temperature
Parameter function
This setting activates the algorithm of compensation of the work
setting:
In cooling mode, the work setting is calculated automatically on
the basis of the outside temperature, following the logic high-
lighted in the diagram.
SF1
SF2
TF1
SC1
SC2
TC1
Parameter function
Parameter function
Parameter function
Parameter function
In heating mode, the work setting is calculated automatically on
the basis of the outside temperature, following the logic high-
lighted in the diagram.
TF2
TC2
SF1: index (6) user menu;
SF2: index (8) user menu;
TF1: index (7) user menu;
TF2: index (9) user menu;
SC1: index (A) user menu;
SC2: index (C) user menu;
TC1: index (B) user menu;
TC2: index (d) user menu;
39

Publicidad

loading