Adjustments of Biox: 
Ten different dosing amounts of chlorine dioxide are available ‐ 0,1 to 2.0 
ppm (parts per million). The dosing amount is stored also in case of power 
cutoff. When power supply is restored the system goes back to its normal 
functions without needing to be reprogrammed. Also in case of battery 
replacement, values remain unchanged. When power supply is restored, or 
when Biox is switched on the selected programming is shown for about 2 
seconds by the illumination of one or two LEDs  (see Tab. 4.8.1). For 
programming: 
 Switch off Biox. 
 Hold down button "Filling confirmation" and at the same time switch 
 
the Biox on again . 
 Press and release in sequence button  "Manual Dosing" until obtaining 
the indication ‐ displayed by the illumination of one or two LEDs ‐ of the 
desired dosing amount  (see Tab. 4.8.1). Normal value: 0,2 ≈ 0,4 ppm. 
 Confirm selection by pressing button "Filling confirmation". 
Biox has now stored the selected dosing amount and is ready for use. The 
LEDs now show the remaining validity time of the chlorine dioxide (in days). 
 
Nota  Bene:  This  adjustment  has  to  be  done  exclusively by  a  manufacturer's  skilled 
engineer. A wrong adjustment might cause the injection of an excessive amount of 
chlorine dioxide into the water which gets undrinkable and excessively aggressive to 
the  equipment  it  flows  through.  The  manufacturer  declines  any  responsibility  for 
damages to property, people, and/or animals caused by wrong adjustments carried 
out by unauthorised staff 
Amount of ClO
 
 
 (ppm)
2
0,1 
0,2 
0,3 
0,4 
0,5 
0,6 
0,7 
0,8 
1,0 
2,0 
32
LED on
LED1
LED2
LED3
LED4
LED5
LED1 e LED6
LED2 e LED6
LED3 e LED6
LED4 e LED6
LED5 e LED6
Tab. 4.8.1