Installation; Installation Conditions - HPN 06 P Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

HPN

Installation

Installation conditions

Installation location
The pool heat pump must be installed outdoors with a distance greater than 3 m
from the Pool according to laws in force (NF C 15 100).
Install the pool heat pump on a flat, horizontal, and stable surface. (Concrete base
would be ideal).
Maintain at least 1 m (40 ") of space on the rear (evaporator air inlet) and 3m (120 ") on
the outlet side of the fan on a completely free space.
Make sure that the discharged air will not be sucked back into the evaporator again.
Provide enough space to allow access to temperature controller.
Outlet air flow:
3 m (120")
Inlet air flow:
1 m (40")
- 34 -

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

08 p10 p12 p15 p

Tabla de contenido