Infosec E4 Serie Manual De Usuario página 36

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

02: Frequency Converter enabled/disabled
Interface
03: Output frequency setting
Interface
04: ECO enable/disable
Interface
05: ECO voltage range setting
Interface
06: Bypass enable/disable when UPS is off
Interface
07: Bypass voltage range setting
Interface
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 03 17 AA XX 209 09
Setting
CF ENA: converter mode enabled
CF DIS: converter mode disabled (Default setting)
Setting
You may set the initial frequency in battery mode:
BAT 50: represents the output frequency at 50Hz
BAT 60: represents the output frequency at 60Hz
If the converter mode is enabled, you may choose the following
output frequency:
CF 50: represents the output frequency at 50Hz
CF 60: represents the output frequency at 60Hz
Setting
ENA: ECO mode enabled
DIS: ECO mode disabled (Default setting)
Setting
Press the Down key or Up key to set the acceptable high
voltage point and acceptable low voltage point:
HLS: High loss voltage in ECO mode.
For 208/220/230/240 VAC models the setting range is
from +7V to +24V of the nominal voltage (Default +12V).
For 110/115/120/127 VAC models, the setting range is
from +3V to +12V of the nominal voltage (Default +6V).
LLS: Low loss voltage in ECO mode.
For 208/220/230/240 VAC models, the setting range is
from -7V to -24V of the nominal voltage (Default -12V).
For 110/115/120/127 VAC models, the setting voltage is
from -3V to -12V of the nominal voltage (Default -6V).
Setting
ENA: Bypass enabled
DIS: Bypass disabled (Default setting)
Setting
36