RPS 15, RPS 30: Power Supply Instruction Manual
RPS 15, RPS 30: Bedienungsanleitung für Stromversorgung
1)
Technical Data
Output Voltage
Factory Setting
Output Current
Output Power
2)
Output Ripple & Noise Voltage
AC Input Voltage
Input Tolerance
Input Frequency
3)
AC Input Current
3)
Power Factor
DC Input Voltage
4)
Input Inrush Current
3)
Hold-up Time
3)
Efficiency
3)
Power Losses
Operational Temperature Range
Output Derating (60°C to 70°C)
Storage Temperature Range
5)
Humidity
, IEC 60068-2-30
Vibration, IEC 60068-2-6
Shock, IEC 60068-2-27
12)
Altitude
Degree of Pollution, EN 50178
Degree of Protection, EN 60529
Class of Protection, IEC 61140
Over-temperature Protection OTP
Output Over-voltage Protection OVP
7)
Touch Current
NEC Class 2
Resistance against Return Voltages
10)
11)
Parallel Use
/ Serial Use
9)
Dimensions
(wxhxd)
Weight
1)
All parameters are specified at 230Vac input voltage, nominal output current, 25°C ambient
and after a 5 minutes run-in time unless otherwise noted.
2)
50 Ohm measurement, bandwidth 20MHz
3)
at 120Vac / 230Vac
4)
A NTC resistor limits the input inrush current after turn-on of the input voltage. The inrush
current is input voltage and ambient temperature dependent. Values are for 40°C ambient.
5)
Do not energize while condensation is present.
6)
PE connection required (Ground).
7)
Leakage (touch) current at 132Vac, 60Hz / 264Vac, 50Hz, TN-mains
8)
Loads such as decelerating motors and inductors can feed voltage back to the output of the
power supply. The figure represents the maximum allowed feed back voltage
9)
Depth without DIN-rail.
10) No current share between the units, ensure that ambient temperature stays below 45°C
11) Use only power supplies of the same type. The total output voltage should not be >150Vdc.
12) Reduce output power (7%/1000m) or ambient temperature (5°C / 1000m) above 2000m sea
level.
Installation
Use DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. Mounting
orientation must be output terminals on top and input terminals on the bottom. For other
orientations see datasheet. Do not obstruct air flow as the unit is convection cooled. Ventilation
grid must be kept free of any obstructions. The following installation clearances must be kept
when power supplies are permanently fully loaded:
40mm on top, 20mm on the bottom of the unit.
Left / right: 0mm (15mm in case the adjacent device is a heat source)
Input Fuses and Input Protection
A 3.15A time delay input fuse is included in the unit (device protection, not externally
accessible). The unit is tested and approved for branch circuits up to 20A. An external
protection is only required if the supplying branch has an ampacity greater than this. Also
check local codes and requirements. If an external fuse is necessary or utilized, minimum
requirements need to be considered. To avoid nuisance tripping of the circuit breaker (if
applicable), use a minimum value of 10A B-Characteristic or 6A C-Characteristic.
Terminals and Wiring
Do not use the unit without PE (Ground) connection! Use appropriate copper cables that are
designed for a minimum operating temperatures of 60°C (for ambient up to 45°C) and 75°C
(for ambient up to 60°C). Follow national installation codes and regulations! Ensure that all
strands of a stranded wire enter the terminal connection! Ferrules are allowed.
RPS 15
Type:
Screw terminal
Screw driver
3.5mm or Pozidrive No 2
2
Solid/Stranded/AWG
0.5-6mm
/0.5-4mm
Wire stripping length
7mm / 0.28inch
Tightening torque
1Nm / 9lb.in
1)
Technische Daten
Ausgangsspannung
Werkseinstellung
Ausgangsstrom
Ausgangsleistung
2)
Ausgangswelligkeit
AC Eingangsspannung
Eingangstoleranz
Eingangsfrequenz
3)
AC Eingangsstrom
3)
Leistungsfaktor
DC Eingangsspannung
4)
Einschaltspitzenstrom
3)
Pufferzeit
3)
Wirkungsgrad
3)
Verlustleistung
Betriebstemperaturbereich
Leistungsrücknahme (60°C to 70°C)
Lagertemperaturbereich
5)
Feuchte
, IEC 60068-2-30
Schwingen, IEC 60068-2-6
Schocken, IEC 60068-2-27
12)
Aufstellhöhe
Verschmutzungsgrad, EN 50178
Schutzart, EN 60529
Schutzklasse, IEC 61140
Übertemperaturschutz OTP
Ausgangsseitiger Überspannungsschutz OVP max. 37Vdc
7)
PE- Ableitstrom
NEC Class 2
8)
8)
Rückspeisefestigkeit
10)
Parallelschaltbar
/ Serienschaltbar
9)
Abmessungen
(BxHxT)
Gewicht
RPS 30
Spring-clamp terminal
not applicable
2
2
/20-10AWG 0.3-4mm
/0.3-2.5mm
6mm / 0.25inch
not applicable
RPS 15
nom. DC 24-28V
typ.
24.5V
nom. 0.63A (24V), 0.54A (28V)
nom. 15W
max. 50mVpp
nom. AC 100-240V
-15% / +10%
nom. 50-60Hz ±6%
typ.
0.28A / 0.17A
typ.
0.51 / 0.44
DC 110-300V (-20%/+25%) DC 110-300V (±25%)
typ.
16A / 31A peak
typ.
47ms / 196ms
typ.
86.1 / 85.1%
typ.
2.5W / 2.7W
-10°C - +70°C
0.4W/°C
-40°C - +85°C
5 - 95% r.H.
2g
30g 6ms, 20g 11ms
0-6000m
2
IP20
6)
I
Yes / Ja
max. 0.3mA / 0.54mA
-
yes / ja
max. 35Vdc
11)
Yes / Ja
nom. 22.5x75x91mm
max. 130g / 0.29lb
1) Alle Werte gelten bei 230Vac Eingangsspannung, Nennausgangsstrom, 25°C Umgebungs-
temperatur und nach einer Aufwärmzeit von 5 Minuten, wenn nichts anderes angegeben ist.
2) 50 Ohm Messung, Bandbreite 20MHz
3) bei 120Vac / 230Vac
4) Der Einschaltstromstoß wird durch einen NTC Widerstand begrenzt. Der Eingangsspitzenstrom ist
eingangsspannungs- und temperaturabhängig. Werte gelten bei 40°C Umgebung.
5) Nicht betreiben, solange das Gerät Kondensation aufweist.
6) PE Verbindung erforderlich.
7) Ableitstrom bei 132Vac, 60Hz / 264Vac, 50Hz, TN-Netze
8) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils
rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an.
9) Tiefe ohne DIN-Schiene
10) Keine Stromaufteilung zwischen den Geräten. Maximale Umgebungstemperatur 45°C
11) Nur gleiche Geräte bis zu einer Gesamtspannung von 150Vdc
12) Reduziere die Ausgangsleistung (7%/1000m) oder die Umgebungstemperatur (5°C / 1000m) über
2000m Aufstellhöhe.
Installation
Geeignet für DIN-Schienen entsprechend EN 60715 oder EN 50022 mit einer Höhe von 7,5 oder
15mm. Der Einbau hat so zu erfolgen, dass sich die Eingangsklemmen unten, und die
Ausgangsklemmen oben befinden. Für andere Einbaulagen siehe Datenblatt. Luftzirkulation nicht
behindern! Das Gerät ist für Konvektionskühlung ausgelegt. Es ist für ungehinderte Luftzirkulation zu
sorgen. Folgende Einbauabstände sind bei dauerhafter Volllast einzuhalten:
Oben: 40mm, unten 20mm vom Gerät.
Links / rechts: 0mm (15mm wenn das benachbarte Geräte eine Wärmequelle ist)
Eingangssicherungen und Eingangsabsicherung
Das Gerät hat eine träge 3.15A Sicherung eingebaut (Gerätesicherung, nicht austauschbar durch
Anwender). Das Gerät ist geprüft und zugelassen zum Anschluss an Stromkreisen bis max. 20A. Ein
zusätzlicher externer Schutz ist nur erforderlich, wenn der Speisestromkreis mit einem höheren Wert
abgesichert ist oder wenn nationale Richtlinien es vorschreiben. Falls ein externes Schutzelement
verwendet wird, soll dieses nicht kleiner als 10A B- Charakteristik oder 6A C- Charakteristik sein um
ein fehlerhaftes Auslösen zu vermeiden.
Anschlussklemmen und Verdrahtung
Betreiben Sie das Gerät nie ohne Schutzleiter. Verwenden Sie geeignete Kupferkabel, die
mindestens für 60°C bei einer Umgebungstemperatur bis zu 45°C und 75°C bei einer
Umgebungstemperatur bis zu 60°C zugelassen sind. Beachten Sie nationale Bestimmungen! Stellen
Sie sicher, dass keine einzelnen Drähte von Litzen abstehen. Aderendhülsen sind erlaubt.
Typ
Schraubendreher:
2
/26-12AWG
Starrdraht/Litze/AWG
Abisolierlänge
Empf. Anzugsdrehmoment
RPS 30
DC 24-28V
24.5V
1.3A (24V), 1.1A (28V)
30W
50mVpp
AC 100-240V
-15% / +10%
50-60Hz ±6%
0.48A / 0.29A
0.61 / 0.53
17A / 35A peak
46ms / 200ms
87.0 / 87.5%
4.5W / 4.3W
-10°C - +70°C
0.8W/°C
-40°C - +85°C
5 - 95% r.H.
2g
30g 6ms, 20g 11ms
0-6000m
2
IP20
6)
I
Yes / Ja
40Vdc
0.23mA / 0.4mA
yes / ja
35Vdc
Yes / Ja
45x75x91mm
230g / 0.51lb
RPS 15
RPS 30
Schraubklemme
Federkraftklemme
3.5mm oder Pozidrive No 2
nicht anwendbar
2
2
0.5-6mm
/0.5-4mm
/20-10 AWG
0,3-4mm
7mm / 0.28inch
6mm / 0.25inch
1Nm / 9lb.in
nicht anwendbar
2
2
/0,3-2,5mm
/26-12 AWG