No. Installer Setting
(
Notes follow this table)
7
1st Stage Differential
8
2nd Stage Differential
[note 2]
9
3rd Stage Differential
[note 2]
10
1st Stage Fan Control
[note 3]
11
Emergency Heat]
Fan Control [note 4]
12
Reversing Valve
(O/B Terminal) [note 5]
13
Fossil Fuel
Backup Heat [note 4]
Compressor Power Outage oF CPOP
14
Protection [notes 4, 6]
15
AC Power Interrupt
Warning [note 6]
16
Compressor Short
Cycle Protection [note 7]
17
Residual Cooling
Fan Delay [note 7]
18
Circulating Fan Lock
19
Adaptive Recovery
Mode (ARM™) [note 8]
20
Indoor Remote Sensor
Control* [note 9]
21
Lockout Security Level
22
Auto Changeover
Dead Band [note 10]
23
Compressor Balance
Point [notes 4, 11]
24
Auxiliary Heat Balance
Point [notes 4, 11]
Factory
Setting
Default
Options
0.5 DIF1
0.5, 1.0 or
2.0 DIF1
2.0 DIF2
1.0, 2.0, 3.0,
4.0, 5.0 or
6.0 DIF2
2.0 DIF3
1.0, 2.0, 3.0, Select a 3rd stage temperature differential of 1°, 2°,
4.0, 5.0 or
6.0 DIF3
HG FAN 1
HG FAN 1
HE FAN 1
HE EMER
HE EMER
HG EMER
REVO
REVO
REVB
AE AUX
AE AUX
AG AUX
oF CPOP
on CPOP
AC oF MONR
AC oF MONR Disables AC Power Interrupt Warning
AC on MONR Enables AC Power Interrupt Warning
5 CSCP
5, 4, 3, 2 or
0 CSCP
60 FAN
90, 60, 30
or 0 FAN
oF CIRC
oF CIRC
on CIRC
oF REC
oF REC
on REC
I SENS
I SENS
E SENS
A SENS
2 LOCK
2 LOCK
1 LOCK
3 BAND
2, 3, 4 or 5
BAND
NO BALC
NO BALC
15-50 BALC Select a Compressor Balance Point of 15°- 50°F
NO BALA
NO BALA
70-40 BALA Select a Auxiliary Heat Balance Point of 70°- 40° F
9
Comments
(More information follows this table)
Select a 1st stage temperature differential of
.5°, 1° or 2° F (0.2°, 0.5° or 1.0° C)
Select a 2nd stage temperature differential of
1°, 2°, 3°, 4°, 5° or 6° F (0.5°, 1.0°, 1.5°, 2.0°,
2.5° or 3.0° C)
3°, 4°, 5° or 6° F (0.5°, 1.0°, 1.5°, 2.0°, 2.5°
or 3.0°C)
Select for 1st stage Gas heating
Select for 1st stage Electric heating
Select for Electric Emergency Heat
Select for Gas Emergency Heat
Select for cool active Reversing Valve (O terminal)
Select for heat active Reversing Valve (B terminal)
Select for Electric Auxiliary heat (with compressor)
Select for Gas Auxiliary heat (without compressor)
Disables Power Outage Lockout Delay
Enables Power Outage Lockout Delay
Select a compressor short cycle protection delay
of 5, 4, 3, 2 or 0 minutes
Select a Residual Cooling Fan Delay of 90, 60,
30 or 0 seconds.
Disables Circulating Fan Lock mode
Enables Circulating Fan Lock mode
Disables Adaptive (early) Recovery mode
Enables Adaptive (early) Recovery mode
Temperature is sensed from thermostat only.
Temperature is sensed from remote sensor only.
Temperature is combined with the thermostat
and the remote sensor.
If locked – Complete lockout is enabled
If locked – Partial lockout is enabled (
is still functional)
Select a Dead Band of 2°, 3°, 4° or 5˚ F
(1°, 2° or 3° C) for Auto Changeover mode.
Disables Balance Points
(-9°-10° C)
Disables Balance Points
(21°- 4°
C)
or
Installer Manual