Technical parameters

LED indication
Green LED RUN:
Red LED ERR:
OLED display
Type:
Resolution:
Visible area:
Controlling:
The internal real-time clock:
Inputs
Inputs:
Outputs
Output:
Number of connected units (directly
to the CU3-01M (02M):
Expansion possibilities external BUS
master:
Communication
BUS
Maximum number of units:
Maximum cable length:
System BUS EBM
Maximum cable length:
Number of connected ext.masters:
Ethernet
Connector:
Communication speed:
Indication of the Ethernet:
The default IP address:
Supply
Supply voltage / tolerance:
Dissipated power:
Rated current:
Operating conditions
Working temperature:
Storage temperature:
Humidity:
Degree of protection:
Overvoltage category:
Degree of pollution:
Operating position:
Installation:
Design:
Terminal:
Dimensions:
Weights:
iNELS RF Control interface
Communication protocol:
Transmitting frequency:
Signal transmission methods:
Output for RF antenna:
RF antenna:
Free space range:
* Max Tightening Torque for antenna connector is 0.56 Nm.
TECHNICAL SUPPORT | E-mail: support@inels.com | Mobil: +420 778 427 366 | Tel.: +420 573 514 276, +420 573 514 211 | Fax: +420 573 514 227 | www.inels.com
Made in Czech Republic
CU3-01M, CU3-02M
fl ashing - communication with BUS;
ON - no communication
fl ashing - no project,
ON - unit STOP
displays the current status and settings
color OLED
128x128 / 1:1 aspect ratio
26 x 26 mm
using arrows
accuracy: 1s/day at 23 °C
4x NO or NC to GND (-) /
2 analogue inputs 0 ÷ 30 V
relay output- NO/GND
max. 64 (2x32)
up to 576 units (CU3-01M (02M) and 8x MI3-02M)
max. 32 units to one BUS line
max. 500 m (depends on power loss)
max. 500 m
up to 8 (regards to increasing the cycle turns)
RJ45 on the front panel
100 Mbps
green - Ethernet communication /
yellow - Ethernet speed 100 Mbps
192.168.1.1 (the IP address can be changed in the
menu using the display and buttons)
27 V DC, -20 / +10 %
max. 3 W
110 mA (at 27V DC)
-20 to +55 °C
-25 to +70 °C
max. 80 %
IP 20 devices, IP 40 with cover in the switchboard
II.
2
any
to the switching board on the EN60715 DIN rail
6-MODULE
2
max. 2.5 mm
90 x 105 x 65 mm
288 g
291 g
CU3-02M
RF Touch Compatible
868 MHz / 915 MHz / 916 MHz
bidirectionally addressed message
SMA connector *
1 dB (part of package)
up to 100 m
ELKO EP, s.r.o. | Palackého 493 | 769 01 Holešov, Všetuly | Czech republic | e-mail: elko@elkoep.com
General instrucions
CONNECTION TO THE SYSTEM, INSTALLATION BUS
iNELS3 peripheral units are connected to the system through the BUS installation. Installation
BUS conductors are connected to the terminal units to BUS+ and BUS- terminals, wires cannot be
interchanged. For installation of BUS it is necessary to use a cable with a twisted pair of wires with a
diameter of at least 0.8 mm, the recommended cable is iNELS BUS Cable, whose features best meet the
requirements of the BUS installation. Bearing in mind that in terms of all the properties is it is possible
in most cases also use the cable JYSTY 1x2x0.8 or JYSTY 2x2x0.8, however it is not recommended
as the best option. In the case of a cable with two pairs of twisted wires it is not possible to use
the second pair of the other for modulated signal due to the speed of communications; it is not
possible within one cable to use one pair for one segment BUS and the second pair for the second
segment BUS. For installation of BUS it is vital to ensure that it is kept at a distance from the power
lines of at least 30 cm and must be installed in accordance with its mechanical properties. To increase
mechanical resistance of cables we recommend installation into a conduit of suitable diameter.
BUS topology installation is free except for the ring, wherein each end of the bus must terminate
at the terminals BUS + and BUS- peripheral unit. While maintaining all the above requirements, the
maximum length of one segment of the installation BUS can reach up to 500 m. Due to the data
communication and supply of units in one pair of wires, it is necessary to keep in mind the diameter
of wires with regards to voltage loss on the lead and the maximum current drawn. The maximum
length of the BUS applies provided that they comply with the tolerance of the supply voltage.
CONNECTION TO THE SYSTEM, BUS SYSTEM EBM
System units MI3-02M, EMDC-64M and GSM3-01M connect to the system through the EBM BUS
system. The BUS system conductors are connected to the terminals EBM+ and EBM-, wires can not
be interchanged. The BUS system EBM is essentially a symmetrical high-speed RS485 interface and,
as such, subject to requirements of the appropriate conduit. When installing the EBM BUS system it is
necessary to observe all the requirements for the installation of the RS485 interface. It is particularly
important to avoid overlapping with power lines (maintain a distance of at least 30 cm) and pay at-
tention to equipment generating emissions when these are located in the vicinity of system units
or the EBM BUS management system. These emissions must be suppressed to a desired level. For
the EBM BUS system it is necessary to use CAT5e UTP cable or higher, or an FTP CAT5e and higher
STP CAT5e or higher. For the EBM BUS management system it is not possible to use JYSTY cable or
iNELS BUS Cable, which are used to guide the installation of BUS. EBM system BUS topology is strictly
linear and there are no branches on the BUS. Both ends of the EMB BUS system require to terminate
by using a resistor with a nominal value of 120Ω resistance. Units CU3-01M, CU3-02M, MI3-02M and
GSM3-01M this resistor is inserted between the terminals and EBM+ EBM-. The unit EMDC-64M resis-
tor is included with the unit and closing is done by shorting adjacent terminals TERM and EBM+.
SUPPLYING THE SYSTEM
For supplying power to system units, it is possible to use the power sources of ELKO EP titled PS3-
100/iNELS. We recommend backing up the system with backup batteries connected to the source of
PS3-100/iNELS (see sample diagram of connecting the control system).
Installation Manual CU3-0xM central unit, installation manual iNELS and confi guration software iDM3
are available for download on the website www.inels.cz section for system partners.
To obtain credentials, please contact us at the email address info@inels.cz.
Warning
Before the device is installed and operated, read this instruction manual carefully and with full
understanding and Installation Guide System iNELS3. The instruction manual is designated for
mounting the device and for the user of such device. It has to be attached to electro-installation
documentation. The instruction manual can be also found on a web site www.inels.com. Attention,
danger of injury by electrical current! Mounting and connection can be done only by a professional
with an adequate electrical qualifi cation, and all has to be done while observing valid regulations.
Do not touch parts of the device that are energized. Danger of life-threat! While mounting,
servicing, executing any changes, and repairing it is essential to observe safety regulations, norms,
directives and special regulations for working with electrical equipment. Before you start working
with the device, it is essential to have all wires, connected parts, and terminals de-energized. This
instruction manual contains only general directions which need to be applied in a particular
installation. In the course of inspections and maintenance, always check (while de-energized) if
terminals are tightened.
2/2