tance of more than 15mm between the power supply and the peripheral parts. When lining up multiple units, please
make sure to place them 15mm or more apart from each other.
2)
Maximum allowable penetration of mounting screws into the power-supply is 5mm except LS25 (4mm).
3)
Recommended torque for mounting screws of LS25 ~ LS150 (M3 screw) : 0.49 Nm (5.0 kgfcm).
6. Wiring Method
The input and output load wires shall be separated and twisted to improve noise immunity.
Both wires must be as thick and short as possible to make lower impedance.
Noise can be reduced by connecting a film capacitor with 0.1uF capacitance across the load terminals.
For safety and EMI considerations, connect the FG terminal of LS series to mounting set ground terminal.
The recommended wire type :
MODEL
LS25
LS35 ~ LS150
Note 1 : When using separate loads, it is recommended to use 2 pieces of 0.8mm thick crimp-type terminal.
Note 2 : For recommended wire diameter, refer to wire maker recommended allowable current and voltage
drop. For higher output current model like 3.3V & 5V, bigger diameter wire is recommended.
7. External Fuse Rating
Refer to the following fuse rating when selecting the external input fuse. Surge current flows when input turns on.
Recommended
Recommended torque
Wire
M3.0 Screws
AWG16-22
0.49 Nm (5.0 kgfcm)
M3.5 Screws
AWG14-22
1.0 Nm (9.8 kgfcm) ~
1.4 Nm (13.7 kgfcm)
Recommended crimp-type terminal
D
(MAX)
6.0mm
6.8mm
11
TDK-Lambda
LS
Series
25-150
INSTRUCTION MANUAL
t
Mounting
(MAX)
Pieces
(MAX)
0.8mm
2 pieces
0.8mm
2 pieces