Ferroli ATLAS D 50 UNIT Instrucciones De Uso página 44

Ocultar thumbs Ver también para ATLAS D 50 UNIT:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 15
Pump pressure adjustment
The pump pressure is factory set for optimum operation and should not normally be
changed. However, if special needs require a different pressure, after applying the pres-
sure gauge and lighting the burner turn the adjustment screw "6" indicated in fig. 24/
fig. 25. It is anyhow recommended to keep within the range of 10 - 14 bar
10
15
5
20
0
25
fig. 24 - SUNTEC pump
fig. 25 - DANFOSS pump
1.
Inlet (suction)
2.
Return
3.
Outlet to nozzle
4.
Pressure gauge connection
5.
Vacuum gauge connection
6.
Adjustment screw
7.
By-pass screw
44
EN
10
15
5
20
0
25
cod. 3541I330 - Rev. 02 - 04/2018
ATLAS D 50 UNIT
Head and air lock
Adjust the head and air flow rate according to the burner power as given in fig. 26
Turn the head adjustment screw B (fig. 27) clockwise or anticlockwise until the notch on
the rod A(fig. 27) coincides with the indicator.
3.79
4.21
4.63
5.17
fig. 26 - Burner adjustments graph SUN G10
A
Power
B
Adjustment indicator
C
Oil flow rate
"L" head (mm)
Air
To adjust the air flow rate, operate the screw C (fig. 27) after loosening the nut D. After
making the adjustment tighten the nut D.
fig. 27 - Burner adjustment
Position of electrodes - baffle
After fitting the nozzle, check correct positioning of the electrodes and baffle, according
to the values given below. It is advisable to check the values after every operation on the
head.
5
fig. 28 - Electrode - baffle position
5.48
5.90
6.32
6.74
7.17
Ø22
7.59

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido