7. Cooling

7.1.
The regulator gets the temperature measure from the thermoregulation probe; the setpoint is 18°C ± 1,5°C for
Water+Glycol units and 26°C ± 1,5°C for OIL units.
Control action is proportional to the error and it reaches saturation (100%) when the temperature is greater than the setpoint
plus the "Hysteresys"/2 = 1,5°C.
Type
Water+Glycol
Oil
All

Cooling with Fixed Setpoint

Compressor Setpoint Settings
Parameter
SEt
SEt
WS
Df1
70040-125_01-_.docx
Factory Setting [°C]
18
26
SEt
3
Range of Setting [°C]
10 - 35
20 - 35
10 - 35
3
7