Scope Of Delivery; Dimensions; Installation Example; Assembly - Franke AQLT0093 Instrucciones De Montaje

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

7.

Scope of delivery

AQLT0093 AQLT0094 AQLT0095
1
1
1
1
2
1
1
8.

Dimensions

9.

Installation example

10. Assembly

Warning!
Only operate the fitting with non-return valves and the specified filters.
Failure to observe this instruction can result in an increased germ load in the
drinking water and thus pose a health or mortality risk.
Important!
Prior to the assembly process, flush the pipework in accordance with DIN 1988.
10.1 Remove the wall protection.
10.2 Use an Allen key to close the water volume regulators.
a: closed
b: open
10.3 Open the locking screws (c) of the water quantity regulators (d).
Important!
Note the installation position of the filters (e).
10.4 Insert the filters (e).
10.5 Screw in the locking screws (c).
Caution!
Use an open-ended wrench to hold the water quantity regulators (d) in position while
turning the cap nuts (f).
tightening torque: 1 Nm
10.6 Remove the T-type flush connector (g) and any seals that are present.
6
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
Name
AQUALINE-THERM DN15 self-closing
thermostat battery
Thermal disinfection option
Automatically emptying shower pipe
Frame with profile seal
Cover plate
Push-on rosette
Bag with filters and seals
Bag with attachment materials
Installation and operating instructions

Publicidad

Tabla de contenido
loading

Tabla de contenido