System Limitations; Maximum Distance Between The Rapid Shutdown Box And The Solar Modules - Fronius Rapid Shutdown Box - Single Manual De Instrucciones

Supervisión del equipo
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

The Rapid Shutdown can be initialized by means of AC failure if the signal lines are con-
nected to the inverter. Alternatively or additionally, an emergency stop button that inter-
rupts the signal wires can be used.
Input 1.1-
Input 1.2-
Input 1.1+
Input 1.2+
System Limita-
Maximum number of Rapid Shutdown Boxes in a system: 5
Maximum line resistance permitted in the signal loop: 300 
tions
Maximum Dis-
tance Between
the Rapid Shut-
down Box and the
Solar Modules
Input 2.1+
RSB Multi
Input 2.2+
Input 2.1-
Input 2.2-
DC-Output 1
DC-Output 2
Conduit size:
3/4 in.
Conduit size:
1 in.
The Rapid Shutdown Box - Single can
connect one string. The Rapid Shutdown
Box - Multi offers the possibility to connect
up to four input strings. These become two
output strings combined.
7

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rapid shutdown box - multiRapid shutdown box-single

Tabla de contenido