2 Safety instructions

2 Safety instructions
The installation and commissioning as well as the connection of electrical components require
technical knowledge commensurate with a recognised vocational qualification as a fitter for
plumbing, heating and air conditioning technology, or a profession requiring a comparable level
of knowledge [specialist].
The following must be observed during installation and commissioning:
Relevant local and national regulations
Accident prevention regulations of the professional association
Instructions and safety instructions mentioned in this manual
Personal injury and damage to property!
The module for return flow temperature maintenance must only be used in hydronic
heating closed-loop systems filled with heating water according to
VDI 2035 / Ö-Norm H 5195-1.
The module must not be used in domestic water applications.
NOTICE
Material damage due to mineral oils!
Mineral oil products cause lasting damage to seals made of EPDM, whereby the sealant
properties get lost. We do not assume liability nor provide warranty for damage to property
resulting from sealants damaged in this way.
 It is imperative to avoid that EPDM gets in contact with substances containing
mineral oils.
 Use a lubricant based on silicone or polyalkylene and free of mineral oils, such as
Unisilikon L250L and Syntheso Glep 1 of the Klüber company or a silicone spray.
2016/03
CAUTION
99961255DeD01-mub-ml – V04
B-4