Press the ENTER key.
With the bottle lifted off the scale plate, press START. The following screen will be displayed:
Place the reference weight (28 to 32 kg) at the centre of the scale plate. Use keys 0 through 9
to type in the value of the weight. Press START. Switch off the machine and disconnect it from
mains supply. Replace the bottle on the scale plate and the heating coil on the bottle (Attention:
the resistance must adhere tightly to the bottle). Replace the cover. Open the blue and red
taps on the bottle. Replace the rear cover.
BOTTLE DATA
N.B. This menu is reserved for use by the technician performing final testing. It contains the
maximum safety threshold value; therefore, the bottle data may not be changed for any reason.
For assistance, call the Service Center.
From the CALIBRATION MENU:
Select BOTTLE SCALE and the following screen is displayed:
Select BOTTLE DATA. The following screen will be displayed:
Use the arrow keys and the number pad to change the Max, Min, and Tare values. Then select
PREVIOUS MENU and press ENTER.
Press START to confirm saving the data or STOP to exit without saving.
INSTRUCTIONS MANUAL
ZERO LEVEL
Raise the bottle
levels
xxxxx
press START
REFERENCE VALUE
xxxxx g
levels
xxxxx
press START
BOTTLE SCALE
OIL SCALE
A/C PRESSURE TR.
BOTTLE TEMPERATURE
CALIBRATION
<BOTTLE DATA>
PREVIOUS MENU
Max
xxxxx g
Min
xxxxx g
Tare
xxxxx g
PREVIOUS MENU
SAVE DATA:
Press START.
To exit:
press STOP
pag.36 - 12/11/2015