Operating Display - Elektrotechnik Schabus SHT 5002 Instrucciones De Uso

Detector de agua (regulación de nivel)
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 43
4.4 S3 sensor warning
With sensor 3, you can determine the water level independent of the level control in order to
obtain e.g. the following warnings:
Overflow warning in the event of pump failure (sensor 3 is installed over sensor 2)
Dry running warning for the protection of the pump (sensor 3 is mounted under sensor 1)
Water level report (sensor 3 is installed between sensor 1 and 2)
4.4.1 Switching behaviour of the K2 relay
Water level below sensor 3 - K2 relay picked up
Water at sensor 3 - K2 relay dropped out
4.4.2 Configuration of the S3 sensor warning
You can define two different output messages for the S3 sensor input:
S3 sensor warning with storage function: The warning persists or the K2 relay stays
switched until a button is pushed to clear the warning.
S3 sensor warning without storage function: The warning persists or the K2 relay stays
switched until the sensor no longer reports water.
Storage function ON with jumper B2
The <Sensor S3> LED and K2 relay must be acknowledged
as soon as the water is no longer in contact with sensor 3.
Storage function OFF without jumper B2
The <Sensor S3> LED goes out and the K2 relay picks up
again as soon as the water is no longer in contact with
sensor 3.
4.4.3 Acknowledgement of K2 relay
The K2 relay can be acknowledged separately with the <RESET> button while the S3 sensor
warning is present. In the process, the <Sensor S3> LED illuminates in red until the water is
no longer in contact with sensor 3.
5. OPERATION

5.1 Operating display

LED <Sensor S3> blinks in red: Water at sensor 3 - K2 relay has dropped out
LED <Sensor S3> illuminates in red: Water at sensor 3 - K2 relay has picked up (acknow-
ledgement)
LED <Niveau S1-S2> illuminates in green: K1 relay dropped out
LED <Niveau S1-S2> blinks in green: K1 relay picked up
S1 S2
B1
13 14 15 16 17 18 19 20 21 22 23 24
S1 S2
B1
WATER DETECTOR
SHT 5002
13 14 15 16 17 18 19 20 21 22 23 24
Sensor S3
Niveau S1-S2
WATER DETECTOR
TEST
SHT 5002
L
N
12 V
Sensor S3
+ -
Niveau S1-S2
1
2
3
4
5
6
TEST
L
N
12 V
L
N
+ -
230 V AC
1
2
3
4
5
6
S3
B2
S3
B2
RESET
K1
K2
7
8
9 10 11 12
RESET
K1
K2
7
8
9 10 11 12
15

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

300749

Tabla de contenido