DESCRIPTION
The SE126K is a gas detector for heating plants, with a catalytic sensor for flammable gas. The unit is for wall in-
stallation and the protection code is IP44. It is normally powered at 230 AC and/or 12÷24VAC/DC.
Two different models are available and the only difference is the calibration carried out with specific gas:
• The SE126KM model should be used in plants using Methane.
• The SE126KG model should be used in plants using LPG.
On the front plate the LED bar shows both the working condition and the gas concentration detected by the sensor.
The detector is supplied with two alarm levels with sealed-type outputs relays and with tension-free change over
contacts. Furthermore it has an auxiliary outputs relays in positive security for FAULT situation and an auxiliary input
(AUX) connectable to our Manual NC Resetting valve with Positioning Sensor.
Fig. 1 shows a typical mains supply wiring diagram with alarm siren and normally closed solenoid valve.
OPERATIONAL DESCRIPTION
Preheating: when the central unit is supplied, the yellow LED starts to flash and it means the sensor is heating.
After 60 seconds, the green LED switches on and it means the normal working.
NORMAL OPERATING: the detector reads the gas concentration through the internal sensor
st
1
Red LED: it illuminates if the gas concentration exceeds 5% LIE.
nd
Red LED (ALARM 1): it illuminates if the gas concentration exceeds 10% LEL; if within 4 seconds the gas is
2
not reduced, the PREAL. relay will activate. This relay is normally used as a prealarm using a siren (SE301A).
rd
3
Red LED: it switch on if the gas concentration exceeds 20% LEL; if the gas persists, the 4
switches on within 30 seconds and the ALARM relay will activate. It is normally used to stop the gas through the
manual reset solenoid valve (NO or NC) and/or the interruption of the electrical energy.
If it has been installed a manual reset solenoid valve N.C. with magnetic sensor (mod. VR420÷VR480) connected to AUX input, in the case that the
gas is still open, the yellow LED and the FAULT Relay will activate (see FAULTS section).
RESET Key: The alarm condition remains latched, LEDs and relays remain activated, even if the gas concentra-
tion is reduced, because the mounted valve is closed. To reset the normal working conditions and/or switch off the
siren push the RESET key.
Buzzer: the PREAL. relay will be deactivated and the red LED flashes, only if the gas concentration is higher than
10% of LEL. After 20 seconds, both of them will return in preallarm. (The siren rings)
If it has been used a manual reset solenoid valve NC with the magnetic sensor and in the case that it is snapped, the yellow LED will switch
off and the FAULT relay will be deactivated. (See FAULTS section).
Alarm RESET: The detector will begin to the normal working, only if the gas concentration is lower than 10% LEL,
the ALARM relay will be deactivated and the 3
deactivated and the yellow LED will switch off. (see FAULTS sections).
Warning: Pushing the RESET button, if the gas concentration is higher than F.S., it can happen that the first
PREAL. relay will be deactivated and the first three red LEDs will switch off. The yellow LED will illuminate and the
FAULT relay will activate. A fault on the sensor is most probable in this case. Eliminate the alarm's cause, if the
condition persist pushing the RESET key, please consult the FAULTS section.
FAULTS: The detector signal different kind of failures activating the yellow LED and the FAULT relay. That is nor-
mally activated. The FAULT relay, if necessary, can be used both to signal remotely an occurred damage and to
signal the absence of power to the instrument.
Yellow and green LEDs and FAULT relay activate: this happens when the catalytic sensor is not working. If this
condition do not change, it will be necessary to replace the unit or to send it to the supplier back to repair.
th
red LEDs, FAULT and ALARM relays activate: (ONLY after press RESET key) this happens
Yellow, green, 4
when the catalytic sensor is not working or in few cases when there is a higher gas concentration. In this case the
detector will remain in alarm, as described in the OPERATING>WARNING section. If there are not any gas leaks
and the condition is not change, it will be necessary to replace the unit and/or send it back to the supplier to repair.
Manual reset solenoid valve NC with magnetic sensor failure: this situation appears ONLY when is installed an electro
valve with magnetic sensor; if it not close the gas, the ALARM relay will activate (gas concentration higher than 20% LIE) and the magnetic
sensor signals to the central unit the this bad working. In this case all led will be lighted and relays will be activated. The failure condition (yel-
low led lighted and FAULT relay activated) will be cancelled if pressing the RESET key, the solution of the problem will be visualized.
INSTALLATION
The SE126K should be installed according to the national disposition in force on the matter.
Model SE126KM positioning: Methane (CH
0.55; its LEL (Lower Explosion Limit) is 4.4% volume. The instrument should be fixed at 30 cm from the ceiling and be
placed at 1-1.5 meter from the gas appliance, far from the room corners or from ventilation intakes.
Model SE126KG positioning: LPG is a gas mixture composed by 20-30% Propane (C
tane (C
H
). LPG calibration must be carried out with Butane which is a combustible gas heavier than air. Its den-
4
10
sity related to air is 2 and its LEL (Lower Explosion Limit) is 1.4% volume. The instrument should be fixed at 30 cm.
TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI )
Istruzione / User's Manual / Manuel d'utilisation
rd
th
and 4
red LED will switch off. If activated, the FAULT relay will be
) is a combustible gas lighter than air. Its density related to air is
4
th
red LED ALARM 2
H
) and by 70-80% Bu-
3
8
Tel: 02/26 92 28 90 Fax: 02/21 33 734
Pag.4/8