ALLTRONIC SEMIS 160 Manual De Instalacion Y Uso página 101

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

ANOMALY:
CODE
A01
A03
A05
A06
A07
A08
A09
A10
A11
A13
A14
A15
A16
A18
A22
A23
A24
A25
A26
A27
A29
A30
A31
A32
A33
A34
A36
A37
A38
A39
A40
//
A47
// = Parallel Anomaly
DESCRIPTION
Incorrect data configuration
Inverter not synchronized
Overvoltage on Phase1 input line
Overvoltage on Phase2 input line
Overvoltage on Phase3 input line
Undervoltage on Phase1 input line
Undervoltage on Phase2 input line
Undervoltage on Phase3 input line
Input frequency out of tolerance range
Voltage on Phase1 bypass line out of tolerance range
Voltage on Phase2 bypass line out of tolerance range
Voltage on Phase3 bypass line out of tolerance range
Bypass frequency out of tolerance range
Voltage on bypass line out of tolerance range
Load on Phase1 > set user threshold
Load on Phase2 > set user threshold
Load on Phase3 > set user threshold
Output switch open
Positive battery branch absent or battery fuses open
Negative battery branch absent or battery fuses open
System temperature sensor fault
System temperature < 0°C
System overtemperature
Phase1 dissipator temperature < 0°C
Phase2 dissipator temperature < 0°C
Phase3 dissipator temperature < 0°C
Internal battery overtemperature
External battery temperature sensor fault
External battery overtemperature
Positive branch batteries must be replaced
Negative branch batteries must be replaced
Different firmware version
- 102 -

Publicidad

Tabla de contenido

Solución de problemas

loading

Productos relacionados para ALLTRONIC SEMIS 160

Este manual también es adecuado para:

Semis 200

Tabla de contenido