Technical Data - Aventics RMV AS-i/DI Instrucciones De Servicio

Acoplador de bus con entradas de sensor
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

English
1
Safety notes
W
The bus coupler is to be used exclusively in bus systems according to AS-i
specifications.
W
This is a class A product. In a living environment this product can cause
radio interference, in which case it may be necessary for the user to take
appropriate measures.
W
Installation should only be done by trained specialists.
W
Only operate the bus coupler in a completely assembled state. Always
turn off the power when plugging and unplugging the plug connectors.
W
The power supply must be installed in such a way that no surge voltages
can occur on the output side.
W
The bus coupler has an integrated watchdog function, which resets the
outputs in the event of a bus communication failure.
2
Addressing the bus coupler
Connect the bus connection (9) to an addressing device using the addressing
cable (see accessories).
Assign an address within a range of 1 to 31 and document it on the
label (6), (12).
The bus coupler address set at the factory is: 0
3
Connecting the bus cable
Connect the yellow profile cable (11) to the plug (9) via the cable socket (10).
Status-LED (4) and (5):
POWER
FAULT
off
off
green
off
green
red
green
flashing red
4
Connecting the sensors
Up to 4 sensor inputs can be connected to the bus coupler using the dual plug
(see accessories).
2
See the figure
for M12 socket (8) assignment.
If LED "I0" to "I3" (7, yellow) is on: the input is high. Inputs I0 to I3 can be read
out with data bits D0 to D3.
5
Triggering the valves
The valves are triggered by the bus coupler's (3) 4 outputs according to the
following allocation scheme.
Allocation scheme: bus coupler
Data bit
Valve location
1
2
D0
solenoid 14
D1
solenoid 14
D2
solenoid 12
D3
solenoid 12
Meaning
No supplyvoltage present at bus
Cyclic I/O data traffic
No I/O data traffic
Short circuit/overload of sensor supply.
S1 status bit is set.
3
4
solenoid 14
solenoid 14
AVENTICS | RMV AS-i/DI | 1987765506–BDL–001–AB
6

Technical data

Characteristics
General
Degree of protection
IP 65 (EN 60529/IEC 529) when assembled.
Ambient temperature
0°C to +50°C
Bus coupler
Rated voltage
according to AS-i specifications 26,5 V ... 31,6 V
Power consumption
40 mA
Current per
50 mA
valve solenoid
I/O-Code
7
ID-Code
F
ID2-Code
E
Sensor supply
Total output of sensors max. 100 mA and current per triggered input 5 mA
(short circuit proof)
Electromagnetic compatibility
Interference signal/
EN 50295
Interference immunity
Accessories (order separately)
Cable socket
1 824 484 064
(1 piece) incl. label
M12 duo plug
1 834 484 246
Addressing cable
on request
7
Figure legend
1 Master
2 Power supply
3 Bus coupler with sensor inputs
4 LED POWER (supply, green)
5 LED FAULT (status, red)
6 Identification field
7 4 LEDs: sensor inputs I0 to I3 (yellow)
8 2 M12 sockets: sensor inputs I0 to I3
9 Plug bus connection (PWR)
10 Cable socket bus connection
11 Yellow profile cable
12 Label