TR120 TOUCH SCREEN WALL MODULES
Do not install the wall module where it can be affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
WHEN USED TO SENSE ROOM TEMPERATURE
Install the wall module about 4 ft. (1.2m) above the floor in
an area with good air circulation at average temperature.
(See Fig. 2.) Confirm mounting height meets Americans
with Disabilities Act requirements, if applicable.
WHEN NOT USED TO SENSE ROOM TEMPERATURE
When using the remote-mounted temperature (and
humidity) sensor(s) to sense ambient conditions, install
the wall module in an area that is accessible for setting
and adjusting the temperature and settings.
NO
NO
Fig. 2. Typical location of wall module
or remote-mounted sensor.
When mounting the wall module to the wall, note the
arrows indicating which direction is up, as indicated on
the inside of the back plate. See the arrows on the
backplate, as shown in Fig 4, indicating the desired UP
position. The wall module can be mounted horizontally or
vertically. The display orientation is determined on initial
power up, and can also be changed at any time.
The wall module can be mounted on a wall, on a standard
utility conduit box using No. 6 (3.5 mm) screws or on a 60
mm wall outlet box (see Fig. 3). When mounting directly on
a wall, use screws appropriate for the wall material. Use a
wall plate, 50028399-001, to cover any visible screw
holes.
31-00275M—01
YES
NO
4 FEET
(1.2 METERS)
M36229
STANDARD UTILITY
CONDUIT BOX
SCREW
Fig. 3. Mounting the wall module to electrical boxes.
WIRING
The wall module is shipped with the front cover and
subbase assembled together. These two parts need to be
separated (see Fig. 4) in order to properly wire the device.
There are no field adjustable/replaceable components
inside the module.
Fig. 4. Separate the front cover from the subbase.
IMPORTANT
All wiring must comply with local electrical codes
and ordinances or as specified on wiring diagrams.
CAUTION
Improper Electrical Contact Hazard
Screw-type terminal blocks are designed to accept
no more than one 14AWG (2.5mm sq) conductor.
2
WALL
OUTLET BOX
SCREW
SCREW
SCREW
M36283
M36296