UL Presriptions
WARNING: Risk of Electric Shock, wait No. 5 minutes before
Only for drive with mark:
The wiring diagram is in section 6.2.
Use with suitable copper (CU) conductor 65°/75°C only.
Maximum surrounding air temperature 0 - 40°C up to 55°C with a linear de-rating
with In (at 55°C) of In/2 and Pout/2 (at 40°C).
The device shall be installed in a pollution degree 2 environment.
Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 Arms
Symmetrical Amperes, 480Vac Maximum.
The ECO TECH series shall be supplied by source of supply center star earthed.
The ECO TECH series has not to be supplied by a corner earthed supply system.
Overvoltage Category: 3 for power board, 2 for logic and control boards.
Integral solid state short circuit protection does not provide branch circuit
protection.
EXTERNAL REQUIRED SEMICONDUCTOR PROTECTION FUSES
Recognized Semiconductor Fuses (JFHR2,JFHR8), see table below for the
manufacturers, model number and electrical ratings of the Fuses analyzed and/or
tested:
SIBA GMBH 50 179 06
COOPER BUSSMANN LLC FWC-25A10F
Values of the Field Wiring Tightening Torque:
! CN1:
30-14 AWG, Cu, 2-4 lb in,
! CN2:
30-14 AWG, Cu, 2-4 lb in,
! CN9:
30-14 AWG, Cu, 2-4 lb in, (optionally),
! M1:
24-8 AWG, Cu, 7 lb in.
! M2:
24-8 AWG, Cu, 7 lb in.
! M3:
24-8 AWG, Cu, TQ N/A,
! M4:
30-14 AWG, Cu, 2-4 lb in.
Motor Overload Protection is provided connecting R/C (XGPU2,XGPU8) sensing
PTC/s, which supplied at 24Vdc has/have a resistance higher than 5K" at the
maximum value permitted by the insulation system of the motor commanded. PTC/s
shall be connected to terminal block CN4 at pin 25, 26.
operating.
25A 700Vac 650 I
25A 600Vac 390 I
2
T
700 A
2
T
700 A