Follow the procedure below to test for proper operation.
To begin, press and hold the
until the display changes (about 3 seconds).
System test
02
Wireless test
04
Return air sensor
10
Heating system
20
Emergency heating
system
30
Cooling system
40
Fan system
70
Thermostat information
(for reference only)
CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection (minimum
off time) is bypassed during testing. To prevent equipment damage, avoid cycling
the compressor quickly.
69-2091EFS—09
M28488A
and
buttons
s
t

System status

0
Off
1
Test radio signal (after a brief pause, screen displays 1-10 to show
signal strength; 5 or higher recommended)
Screen displays return air temperature if device is installed and
working properly
0
Heat and fan turn off.
1
Heat turns on
2
Stage 2 heat turns on
3
Stage 3 heat turns on
0
Heat and fan turn off
1
Heat and fan turn on
0
Compressor and fan turn off
1
Compressor and fan turn on
2
Stage 2 compressor turns on
0
Fan turns off
1
Fan turns on
71
Software revision number (major revisions)
72
Software revision number (minor revisions)
73
Configuration identification code (major)
74
Configuration identification code (minor)
75
Production configuration date code (week)
76
Production configuration date code (year)
12
System test number
02
Done
Back
Press
or
s
t
NEXT
Press
to advance to next test
DONE
Press
to terminate system test
System status
0
Next
to check system status
M28489