Name of each part
Name of each part
LONWORKS GATEWAY
BUS_A: 485 communication line A (+)
1
BUS_B: 485 communication line B (-)
2
F1, F2: Fire detection function (external device) contact point connection
3
LAN: LAN port necessary for web function
4
5
LON: TP/FT-10 communication line (Lonworks system communication line) non-polarity
6
PWR: Connection to DC 12V power adapter
7
12V: Connection when not using DC 12V power adapter
8
GND: Connection when not using GNS adapter
ALIVE/WINK: It flashes every 1 second when it is normal
It flashes 5 times when receiving WINK command from Lonworks system
(Green)
SERVICE: It is turned off when it is normal and flashes when it is not connected to the
Lonworks system. It is turned on when the service switch is pressed.
SERVICE SWITCH: When you press the switch the Neuron ID is transmitted to the
BNU-LW (PNF-B16A1) product is a product certified of LON-MARK, an international
standard. (Lon Mark Version 3.3)
No. 6 and No. 7,8 are all for power supply. Therefore, only one of two combinations should be used.
When DC 12V is used for the power, Connect No. 6 to the power (not necessary to use No. 7,8.)
When DC 12V is NOT used for the power, Connect No. 7, 8 to the power (not necessary to use No. 6.)
10 Lonworks Gateway
Lonworks system, and the service LED is turned on.
1
2
3
4
5
6
7
8