2-wire Prestige® IAQ and RF EIM
Installer setup tables
Setup functions
100
Language
110
Zone Number
112
Device name
130
Date
160
Schedule options
172
System selection
173
Heat Pump Type
174
Stages
175
Series 20 Control
180
Fan operation
190
Reversing valve
200
Backup heat
210
External fossil fuel
220
Compressor cycle rate(s)
240
Heat stage cycle rate(s)
300
Changeover
310
Deadband
320
Temperature display
330
Daylight savings time
1350
Configurable S1 Sensor Input
1355
Configurable S2 Sensor Input
342
Outdoor temperature sensor?
346
Upstage timer
347
Droop Temperature
349
Backup Heat Control
350
Compressor lockout (balance point)
360
Auxiliary lockout
365
Discharge Air Temperature Sensor
1400
Configurable U1 Relay
1405
Configurable U2 Relay
1410
Configurable U3 Relay
371
Humidification equipment
372
Indoor humidity control
374
Humidifier fan action
379
Dehumidification equipment
1500
Low Speed Fan Position
383
Overcooling limit
384
Dehumidification fan control
386
Whole house Dehumidification Lockout
390
Dehumidification away mode
391
Away mode fan operation
392
Away mode low temp. setting
393
Away mode high temp. setting
394
Away mode dehumidification
400
Ventilation Control
401
Number of Bedrooms/Size of home
403
Ventilation levels
405
Ventilation Fan Action
406
Ventilation in High Humidity
69-2445EFS—03
(factory default setting listed, other options available)
10
English
Not Zoned
Thermostat
Month, Date, Year
Programmable
Conventional
Air To Air
1 Heat/1 Cool
No
System (gas/oil/heat)
O/B on Cool
Electric
Yes
3
5
Manual
2° F
Fahrenheit
Auto change: On
None
None
No
Off
2
Comfort
Off
Off
No
None
None
None
None
Off
Humidify only with fan
None
Normally Closed
3° F (1.5° C)
Forces fan on
Off
Off
Automatic
76° F (24.5° C)
85° F (29.5° C)
65% relative humidity
Off
2 (1000 sq. ft.)
160 cfm (50%)
Ventilation Forces Fan On
On