Captive Fastener
Power Door
4
WIRING
• NOTE: Make all electrical connections in accordance
with the National Electrical Code and any applicable
local code requirements.
• NOTE: Verify that supply voltage is correct by
comparing it to nameplate.
UL Units:
• Terminals are readily accessible on terminal board
and will accept service leads ranging in size from
AWG No. 16 through No. 6.
• Service leads (See fixture labeling for supply wire
temperature rating) should extend through mounting
bracket approximately 7 inches.
• Attach service leads to terminal board as shown on
luminaire nameplate.
• See table below for screw torques (See Table 1).
• Dimming Control Connections (See Table 2).
• A wiring diagram is provided on a label in luminaire.
Door Latch
TABLE 1. Terminal Board Torque Table UL Units
Wire Range Copper
Aluminum
10 - 16 SOL, STR
8 - 6 SOL, STR
STR6 SOL, STR
TABLE 2. Dimming Control Connections
O VDC (-)
Gray Lead
Up to 10 VDC (+)
Violet Lead
IEC Units:
• Power supply cable and dimming control cable (if
necessary) must be provided by customer.
• Power supply cable (each conductor: phase, neutral
and ground) should be maximum of 12AWG (2.5mm
and minimum of 16 AWG (1.5mm
with an overall cable diameter within the range of 7-12mm.
• Dimming control cable (0 to 10 VDC) (each conductor:
positive and negative) should be 18 AWG (1.0mm
solid or stranded with an overall cable diameter
within the range of 5-10mm.
Terminal Board Connections:
Terminal Board Position
L1
G
N/L2
5
PhOTOELECTRIC CONTROL
• When used, photoelectric (PE) receptacle should be
oriented so that the word "North" is directed toward
true north.
• This is done by seating a PE control into receptacle,
lifting upward on PE control (which will lift PE
receptacle also), and rotating them clockwise until
word "North" is directed toward true north.
• Then lower PE control and receptacle to firmly seat
them into position. No tools are required to make this
adjustment.
• Alternatively, PE receptacle can be oriented
before PE control is installed. This is done by lifting up
on rim of the PE receptacle and rotating it until the
word "North" is directed toward true north.
• Lower PE receptacle to firmly seat it in this position.
Then install PE control.
Torque (in lbs)
30
45
)
2
) solid or stranded
2
)
2
Supply Type
High Line
Ground
Low Line/Neutral