Installation instructions
FlowBox Solar 7000
Flow volume adjustment (Fig. 2)
- The flow volume is set on the regulating valve using an SW 4 Allen
Key.
- The set volume can be directly read on the scale.
- The valve stroke is spread over several spindle revolutions, thereby
permitting a high level of setting precision.
- The setting values are based on the calculations for the system.
Fig. 2
Gravity brake (Fig. 3)
- For filling, flushing and draining the system, the gravity brake must be
open. It is opened by turning the ball valve to the 45° position.
For normal operation of the system, the ball valve must be completely
open.
Fig. 3
0° = ready for
operation
Caution
Pressure and temperature should be kept within the limits shown in the
adjacent diagram. Avoid temperatures higher than 100°C during
continuous operation!
Pressure Tempe
/
Operating Temperature TB (°C)
EDP No. 7010019
Last revised: 20/01/2006
Subject to technical modifications
Litres/min
45° = open
90° = closed
rature
Diagam
Torque for connections with flat seals
Torque values when tightening the screw connections using Reinz AFM 34
gaskets,thickness 2mm:
3/4" Screw connection 35 Nm
1"
Screw connection 55 Nm
1 1/4" Screw connection 90 Nm
1 1/2" Screw connection 13 0 Nm
As the gasket may settle over time, it may be necessary for the customer
To re-tighten the screw connections.
Technical data
Fittings
Pipe systems
Flowmeter
Spring - flowmeter
Heat insulation cladding
Materials
Max. adm. operating temperature : see Pressure/Temperature Diagram
Min. adm. operating temperature : 20°C
Max. adm. operating pressure
Indicating accuracy -
WattFlow
Gesamtdruckverlust
Solar 7000
1.000
100
10
1
10
100
Durchflluss [L/h]
GB
F
: hot-pressed brass, Ms58
: precision pipes
: high-grade impact-proof and
temperature-resistant plastic
: stainless steel
: EPP
: see Pressure/Temperature Diagram
: 10% of the meter reading
+
mit DRS 0,5-7L/min
Kvs = 1,25 m³/h
mit DRS 2-16L/min
Kvs = 2,25 m³/h
Kvs = 2,5 m³/h
mit DRS 4-36L/min
1.000
10.000
flow rate [L/h]