"Regumaq X-80"
¡Los puntos que no se han
llevado a cabo o que han sido
respondidos con un "No" tienen
que justificarse en el campo
"Comentarios"!
Controller equipped with an SD
06.
card for data recording?
Green glowing ring around the
07.
menu button?
Further modifications to the
08.
controller settings?
Repair
(only has to be completed in case of a replacement of components)
01.
Replaced component
Reason for the replacement
01.1
02.
Replaced component
Reason for the replacement
02.1
03.
Replaced component
Reason for the replacement
03.1
Functional control according
04.
to installation instructions after
repair?
Information given to the user of the system / Handover
The installer informed the user of the system about
- the function and correct use of the fresh water station
- the normal operation of a potable water installation
The necessary documents were handed over to the user of the system
Information on the normal operation of potable water installations:
- Stagnation must be avoided, the potable water has to be exchanged at regular intervals
- The potable water temperature at the hot water outlet must not drop below 60 °C
- The circulation system has to be designed so that the potable water temperature is not undercut
by more
than 5 K compared to the outlet temperature of the station of 60 °C
- The potable water temperature at the cold water outlet must not exceed 25 °C
Installer
________________________
Date / Signature / Stamp
Maintenance report received (to be signed by the user of the system)
________________________
Date / Signature