Components
Detector
2 x AAA - LR03/1.5V battery
Velcro
Instructions in three languages
Operating mode
The device automatically enters rest mode except when
installing batteries for the first time. In this case the test
button must be pressed to switch the device on.
Basic operation
When the operator approaches an electric field between
10kV and 66kV and exceeds an approximate distance of
1m for 10 kV and 3m for 66kV, the detector emits a sound
to warn that the operator is in a danger area. The alarm will
not stop until the operator moves away from the voltage
source.
The voltage detectors remains always in alert mode. When
it sounds it can be silenced just knocking two times the
helmet and it will come back to the alert mode.