ART. 20046604 - SIMPLEHOME MODULE WITH 5 OPTICALLY COUPLED INPUTS
AND 4 X 16A RELAY OUTPUTS ON DIN RAIL (5I4O16A)
Module on bus has 4 inputs + 1 scenario input, as well as 4 relay outputs with switching contact with independent common capable of
controlling resistive electrical loads up to 16A. For non-resistive loads, it is best to use a support contactor at each output.
Power supply voltage
Absorption
Inputs
Outputs
Max. input cable length
Protection
Indications
Lack and restoring of
power supply
Terminals
Positioning
Applicable standards
Approvals
Operating temperature
Storage temperature
Relative air humidity
Weight
Dimensions
green (bus)
red (+)
blue (-)
4
TECHNICAL CHARACTERISTICS
24 Vdc ± 5%
min. 5 mA, max. 140 mA
4+1, optically coupled digital type
4 relay 230 Vac, resistive 16A (cos ϕ = 1)
25 m
against reverse polarity
1 bus status indicator LED: when fl ashing, indicates data transmission via bus, when lit steadily
indicates lack of power supply negative or incorrect device connection
5 input status indicator LEDs
4 output status indicator LEDs
Output status memory
removable for BUS connection
On a DIN rail on a dedicated control panel or in junction boxes*
electromagnetic compatibility: EN 50081-1 (interference emission) and EN50082-2 (resistance
to interference)
CE
0° to 50°C
-10° to +70°C
5 to 95% with no condensation
195 g (not including packaging)
71x90x58 mm (4 DIN modules)
* With access allowed only for support or servicing by qualifi ed personnel
Term.
-
BUS power supply negative
+
BUS power supply +24 Vdc
D
BUS data line
K
Common
V-
Support negative
V+
+24 Vdc support
I4
Input 4
Input 3
I3
Input 2
I2
Input 1
I1
Multiple command (scenario)
IS
Output 1 – NO contact
NO1
N.B. The module must be programmed vis the BUS line, using the SimpleHome/RS232
interface (20022611) and the SimpleProg programming software.
Specifi cations are subject to change without notice.
CONNECTION TERMINALS
Function
Term.
C1
NC1
NO2
C2
NC2
NO3
C3
NC3
NO4
C4
NC4
Function
Output 1 – Common
Output 1 – NC contact
Output 2 – NO contact
Output 2 – Common
Output 2 – NC contact
Output 3 – NO contact
Output 3 – Common
Output 3 – NC contact
Output 4 – NO contact
Output 4 – Common
Output 4 – NC contact