automatically shut off.
Input for 24 VDC of inverter, when the battery voltage
reach 20.0 + /-0.5 V, inverter AC output would
automatically shut off.
2) high voltage shutdown
Inverter set up inside high voltage shutdown function,
when the battery voltage to reach set, inverter AC output
would automatically shut off.
For example:
Input for 12 VDC of inverter, when the battery voltage
reach 15.0 + /-0.5 V, inverter AC output would
automatically shut off.
Input for 24 VDC of inverter, when the battery voltage
reach 30.0 + /-0.5 V, inverter AC output would
automatically shut off.
3) Overload protection
Inverter internal Settings are over load protection
function, when load power or electric start-up power too
much, inverter AC output would automatically shut off.
when reduce load power automatically, and restore
output.
For example:
Power for 400W of inverter, when load power more than
400W,inverter AC output would automatically shut off.
21