Descargar Imprimir esta página

Possible Problems And Solutions; Technical Specifications - Meta System WHAD 800 Manual De Uso

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 24

POSSIBLE PROBLEMS AND SOLUTIONS

Problems
• When the UPS is switched on, the buzzer sounds
and the red Status Indicator makes intermittent
short-long flashes, then the UPS switches off
after 15 seconds
• The UPS works but every 20 seconds there is a
short beep and the yellow Status Indcator is
always lit up.
• The UPS works but it emits an alternating, slow-
fast intermittent sound, the red Status Indcator
flashes fastly
- The UPS beeps continuously and the Status
Indicator is continuosly yellow, after which the
UPS switches off.
• The UPS works but the green Status Indicator
flashes quickly
• The UPS emits an alternating, slow-fast
intermittent sound, and the red Status Indicator
flashes quickly
Solutions
- The connection of the neutral conductor is wrong:
make a 180° inversion of the power supply plug,
or exclude the neutral sensor (using the UPS
Communicator software supplied)
- Check that power is present at the mains socket.
- Check that the UPS power supply cable is
correctly inserted in both the mains socket and
in the UPS connector
- There is an overload on the UPS output. Reduce
the quantity of appliances connected so that the
load does not exceed the maximum power that
the UPS can supply.
- The UPS has completely flattened its batteries; it
can only start up again when the input line is
present.
Check
the
magneto-thermal
differential switches that precede the UPS
- The mains supply is out of the limits permitted for
the voltage and/or frequency, but it can still be
used by the UPS. However, the bypass function
is not operational.
- The thermic protection has intervened. Switch the
UPS off and wait for a few minutes so that the
internal temperature of the UPS can get back to
normal. Check that the fans operate correctly
and that the relative airflow is not obstructed
(e.g. if the UPS is too close to a wall).
- There is a fault on one of the internal circuits.
Contact your nearest service centre.
16
Construction specifications
Weight
Size W x D x H in mm
Technology
Computer interface
Protection features
Internal, synchronised bypass
Environmental specifications
Maximum altitude for storage
Storage temperature range
Operating temperature range
Range of relative humidity for operation
Grade of protection according to IEC529
Noise level at 1 metre
or
Nominal input voltage
Nominal input voltage
Range of input voltage
Nominal input frequency
Nominal input current
Maximum input current
Distortion of input current
at 100% of nominal load
Input power factor
Overload current
Number of input phases
Line fuse
Battery charger direct from mains

TECHNICAL SPECIFICATIONS

WHAD 800
12 Kg.
88 X 390 X 355
PWM high frequency both for input stage and output stage.
Microprocessor control logic
Standard serial RS232 for interfacing with personal computer
using the diagnostic software that can be downloaded free of
charge from the website www.metasystem.it, output to 9 pin,
female, SELV insulated, DB9 connector
Electronic protection against overloads, short circuits and
excessive battery discharge.
Operation block at end of autonomy.
Inrush current limitation when switching on.
Sensor for correct neutral connection
Back feed protection (electrical insulation for the safety of
the input plug during operation in battery mode)
Automatic
Intervenes in case of overload and operation anomaly
1000 metres
from -20°C to +50°C
from 0°C to 40° C
From 20% to 80% non condensing
IP21
< 40 dBA
230V
From 184V to 265V with nominal load
From 110V to 265V with 50% of nominal load
50Hz/60HZ +/- 5% selectable by the operator
3 Arms
3.7 Arms
<3%
>0.99 at 80% of nominal load
from 20% to 100% of nominal load
100% of nominal current
Single phase
Automatic Resettable 10 A
Deeply discharged batteries are recharged in 12 to 15 hours
when mains power is present, even should the UPS not be
operating.
17
WHAD 1000
3,5 Arms
4,5 Arms

Publicidad

loading

Este manual también es adecuado para:

Whad 1000