PRCA-BAC-S2-T-250
Controles de funcionamiento e indicadores
Auxiliary switch settings
A
10°
S1
S2 S3
S5 S6
S5 S6
S4
S4
2
1
10°
S1
3
S2 S3
S5 S6
S5 S6
S4
S4
S1 S2 S3
S4 S5 S6
4
Push-button and display
www.belimo.com
Actuador rotativo, proporcional, comunicativo, híbrido,
AC 24...240 V / DC 24...125 V, 160 Nm, Tiempo de giro del
motor 35 s
Note: Perform settings on the actuator only in deenergised state.
For the auxiliary switch position settings, carry out points
1
Gear disengagement
Opening the manual override cover and adjusting the hand crank.
Manual override is possible.
2
Manual override control
Turn the hand crank until the desired switching position
crank.
S2 S3
S5 S6
S5 S6
S4
S4
3
Auxiliary switch
For the auxiliary switch position settings, carry out points
Opening the auxiliary switch adjustment cover and adjusting the hand crank.
Turn the crank until the arrow points to the vertical line
4
Terminals
Connect continuity tester to S4 + S5 or to S4 + S6.
If the auxiliary switch should switch in the opposite direction, rotate the hand crank by 180°.
5
Push-button and LED display green
Off:
On:
Press button:
5
Power
6
Push-button and LED display yellow
Off:
Status
On:
6
Flickering:
Flashing:
Press button:
PRCA-BAC-S2-T-250 • es-es • 2019-11-27 • sujeto a cambios
No power supply or malfunction
In operation
Triggers test run, followed by standard mode
Standard mode
Test run active
BACnet / Modbus communication active
Request for addressing from MP master
Confi rmation of the MP addressing
to
successively.
1
4
A
is indicated and then remove the
to
successively.
1
4
9