Linear LED Battery Back-up Unit for MLL/DLL Series
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
Install in accordance with 46CFR111.75-15 and 46CFR112 for emergency marine
equipment. Battery back-up remote mounted module for LED linear MLL/DLL Series
rated 29W min. to 67W max. suitable for use in the following hazardous (classified)
locations as defined by the National Electrical Code (NEC
NEC/CEC:
• Class I, Division 2, Groups B, C, D
• Class II, Division 2, Groups F, G
• Wet location, Type 4X
• Ambients: -20°C to 55°C
UL STANDARDS:
• UL844 Hazardous (Classified)
• UL1598 Luminaires, UL1598A Marine
• UL924 Emergency Lighting
To avoid the risk of fire, or electric shock, this product should be installed,
inspected and maintained by a qualified electrician only, in accordance with all
applicable electrical codes.
To avoid electric shock:
Be certain electrical power is OFF, to both the battery backup unit and luminaire,
before and during installation and maintenance.
Battery back-up unit must be used with approved wiring and connection methods
suitable for Class I, Division 2 or Zone 2 per NEC/CEC.
To avoid explosion:
Make sure the supply voltage is the same as the input voltage rating marked on
the battery back-up unit.
Do not install where the marked operating temperatures exceed the ignition
temperature of the hazardous atmosphere.
Do not operate in ambient temperatures outside of the marked ambient range on
the battery back-up unit nameplate.
Use only replacement parts from Eaton.
Use proper supply wiring with temperature ratings as specified on the battery
back-up unit nameplate.
All gasket seals must be clean.
Before opening, electrical power to the battery back-up unit must be turned off.
Keep tightly closed when in operation.
INSTALLATION
Requires four (4) 3/8" mounting bolts (hardware not provided) to attach the battery
back-up unit to a surface (ceiling or wall).
MOUNTING
1.
Make sure the power is disconnected to the conduit system before installing
the battery back-up unit.
2.
The battery back-up unit may be mounted to a ceiling or wall using the welded
mounting tabs on the outside of the enclosure (see Figure 1). Select a
mounting location that will provide suitable strength and rigidity for supporting
the battery back-up unit.
3.
The wiring between the battery back-up unit and the linear LED fixture must
not exceed 50 feet. Select a location near the fixture that will accommodate
the wiring limit. The wiring between the battery back-up unit and the LED
fixture should not exceed 50 feet. Since the battery back-up unit is able to be
remote mounted, ensure that the hazardous location selected is suitable for
the ratings on the battery back-up unit.
4.
Do not mount as part of a pendant mounting conduit installation; mount to a
ceiling or wall only.
5.
Use 3/8" size hardware to securely mount enclosure box to desired location.
See Table 1 and Figure 1 for mounting pattern dimensions.
6.
With the battery back-up unit securely fastened to the mounting surface, attach
the conduit or cable system to the enclosure via the entry hubs. Use Eaton's
Crouse-Hinds series HTL on NPT threads to prevent water ingress. If non-
metallic conduit is used install per NEC Article 501.10B1 (b), use conduit and
fittings covered by the NEC suitable for wet locations.
7 .
Apply the provided "mounting height" label to the MLL/DLL luminaire so that
the label is visible after installation of the luminaire.
IF 1740 • 11/15
):
®
WARNING
WARNING
WARNING
Copyright © 2015, Eaton's Crouse-Hinds Division
CSA STANDARD:
• CSA C22.2 Nos. 250, 137, 141
*If stored or charged outside specified temperature range, then potential of reduced
run time, etc.
Battery back-up enclosure construction is designed for use indoors and outdoors in
marine and wet locations, where moisture, dirt, corrosion, vibration and rough usage
may be present.
INPUT VOLTAGE:
EM UNV1 Battery back-up kit
EM UNV34 Battery back-up kit
UNV1 - 100-240, 277 VAC 50/60 Hz
UNV34 - 347/480 VAC 60 Hz
(EM UNV1 Shown)
Battery Back-up
Enclosure Size
Model
(HxWxD) (inch)
EM UNV1
12x12x6
EM UNV34
16x12x6
WIRING
BATTERY BACK-UP UNIT
1.
Open the battery back-up unit using a flat head screwdriver to rotate the latch
¼ turn CCW (see Figure 1).
2.
Locate the terminal block per Figure 2 or 3.
3.
Wire the branch circuit input power to the terminal block per Figure 4 or 5.
Wire the equipment grounding conductor to terminal 7 first, the common to
terminal 8 next, and the line voltage to terminal 9 last.
4.
Connect a pair of wires to the terminal block that will be used to power up the
LEDs on the fixture's LED board. See Figure 4 or 5. Connect the positive wire
to terminal 1 and connect the negative wire to terminal 2.
5.
If dimming is required:
a. Select a dimmer control with location ratings suitable for its selected
mounting location. Rated 0-10 VDC +/- 10%.
b. Locate the dimming control signal input terminal block per Figures 2 and 3.
c. Wire the dimming control signal wires per Figure 4 or 5.
d. Remove the optional control jumper on the charger driver board. If the
dimming control voltage is set too low, some flickering of the LEDs may
occur. If this happens, raise the minimum value of the analog dimming
voltage.
Figure 2. EM UNV1
Configurations
IF 1740
Figure 1
Fixing Center Horizontal
Fixing Center Vertical
Inch (mm)
Inch (mm)
9.49 (241)
13.23 (336)
9.49 (241)
17 .25 (438)
Table 1
Page 1

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Eaton CROUSE-HINDS EM UNV1

  • Página 1 See Table 1 and Figure 1 for mounting pattern dimensions. With the battery back-up unit securely fastened to the mounting surface, attach the conduit or cable system to the enclosure via the entry hubs. Use Eaton’s Figure 2. EM UNV1 Crouse-Hinds series HTL on NPT threads to prevent water ingress.
  • Página 2 1 and battery 2 per Figure 4 or 5. Ensure the red and black wires are aligned correctly on each connector. Figure 6 IF 1740 • 11/15 Copyright © 2015, Eaton’s Crouse-Hinds Division Page 2...
  • Página 3 There is also also be obtained through your local Eaton representative or the Eaton Sales Service a red light that should always be off. In the event that this is on, the circuit board Department, 1201 Wolf Street, Syracuse, New York 13208, Phone 866-764-5454.
  • Página 4: Important Safeguards

    All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Eaton’s Crouse-Hinds Division’s “Terms and Conditions of Sale,” and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
  • Página 5 Utilice Crouse-Hinds Serie HTL de Eaton en las roscas NPT para evitar la entrada de agua. Si se utiliza un conducto no metálico, instale según el Artículo 501.10B1 del NEC (b), utilice el conducto y accesorios cubiertos y apropiados para lugares húmedos según el NEC.
  • Página 6 1 y 2 según la Figura 4 o 5. Asegúrese de que EM a instalación linear de 2 pies los cables negro y rojo se encuentren alineados correctamente con cada conector. Figura 6 IF 1740 • 11/15 Copyright © 2015, Crouse-Hinds Division de Eaton Página 6...
  • Página 7: Mantenimiento General

    REEMPLAZO DE LA BATERÍA Si se utiliza el atenuador analógico, Solo el MLL EM BATTERY PACK de la Serie Crouse-Hinds de Eaton es aceptable como la tensión de control puede bajar lo batería de reemplazo. suficiente lo que puede causar la Desconecte la alimentación de la unidad EM.
  • Página 8: Dimensiones

    En conformidad con los “Términos y condiciones de venta” de Crouse-Hinds y dado que las condiciones de uso están fuera de nuestro control, el comprador debe determinar la idoneidad del producto para su uso previsto y asume todo riesgo y responsabilidad con relación al mismo. Crouse-Hinds Division de Eaton IF 1740 1201 Wolf Street Syracuse, Nueva York 13208 •...
  • Página 9 Lorsque la batterie de secours est solidement fixée à la surface de montage, fixer le système de conduit électrique ou le système de câbles aux plots d’entrée du boîtier. Appliquer du lubrifiant Crouse-Hinds de la série HTL d’Eaton sur le filetage NPT pour empêcher les infiltrations d’eau. Conformément à l’article 501.10 B1 (b) du NEC, si des conduits non métalliques sont utilisés, installer des conduits et raccords...
  • Página 10: Batterie De Secours Connectée À Un Luminaire

    EM connecté à un luminaire linéaire de 61 cm (2 pi) conformément à la figure 4 ou 5. S’assurer que les câbles rouge et noir sont alignés correctement sur chaque connecteur. Figure 6 IF 1740 • 11/15 © Eaton’s Crouse-Hinds Division, 2015 Page 10...
  • Página 11: Essais Périodiques

    REMPLACEMENT DE BATTERIE Si aucun gradateur n’est utilisé et que le cavalier est installé, la carte de circuits Seul le MLL EM BATTERY PACK de la série Crouse-Hinds d’Eaton peut servir de imprimés pourrait être en mauvais état batterie de remplacement.
  • Página 12: Mesures De Protection Importantes

    Conformément aux conditions de vente de Crouse-Hinds, et étant donné que les conditions d’utilisation sont hors de notre contrôle, l’acheteur doit déterminer si le produit convient à l’utilisation prévue et en assume tous les risques et toutes les responsabilités associées. Eaton’s Crouse-Hinds Division IF 1740 1201 Wolf Street, Syracuse, New York 13208 •...

Este manual también es adecuado para:

Crouse-hinds em unv34

Tabla de contenido