Conventional zone output wiring for standard application is
shown in Figure 3:
1.
Conventional zone output
2.
Conventional detector
3.9 kΩ, end-of-line resistor
3.
The conventional zone output requires an end-of-line resistor.
Conventional loop impedance/loads for standard installation
are shown in the table below.
Short circuit
Zone voltage < 12.5 VDC
Fire
Zone current > 19.5 mA
Zone voltage > 4 VDC
Fault
9 mA to 15 mA
Normal*
3.36 mA to 7 mA
Open circuit
< 2.6 mA
* Including all devices and the 3.9 kΩ EOL resistor.
Intrinsically safe installation wiring
Connect the module to the fire panel using the COM2 (positive)
and COM1 (negative) inputs as shown in Figure 2.
Conventional zone output wiring for intrinsically safe
application is shown in Figure 4:
1.
Conventional zone output
2.
GBX2000 barrier
3.
Conventional detector (IS)
5.6 kΩ end-of-line resistor
4.
The total detector current load on the conventional zone after
the GBX2000 barrier must not exceed 1 mA (typically 20 × 670
series IS detectors).
Conventional loop impedance/loads for intrinsically safe
installation are shown in the table below.
Short circuit
Zone voltage < 11 VDC
Fire
Zone current > 19.5 mA
Zone voltage > 12 VDC
Normal*
3.36 mA to 5.7 mA
Open circuit
< 2.6 mA
* Including all devices and the 5.6 kΩ EOL resistor.
Addressing
Each module must be assigned an address from 1 to 128. Use
the rotary dial marked 0 to 12 to set the tens and hundreds part
of the address, and the rotary dial marked 0 to 9 for the
remaining digits. See Figure 5 for sample address settings.
Note:
To overcome the mechanical effects of shipping and
storage we recommend that you first rotate each dial counter-
clockwise (to the 0 position) and then clockwise (to the dial's
maximum position) before setting the required address.
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
P/N 55370172 • REV 05 • ISS 30OCT13
Specifications
Operating voltage
Current consumption in standby
Current consumption in alarm
Remote LED current
Loop capacitance
Line resistance:
< 100 Ω
240 Ω to 620 Ω
End-of-line resistor:
1.2 kΩ to 1.4 kΩ
Operating temperature
2.7 kΩ to 4.3 kΩ
Storage temperature
> 15 kΩ
Relative humidity
(noncondensing)
Dimensions
Weight
Regulatory information
This section includes both regulatory information and a
summary on the declared performance according to the
Construction Products Regulation 305/2011. For detailed
information refer to the product Declaration of Performance.
Certification
Certification body
Declaration of
Performance number
Year of first CE
marking
< 50 Ω
Product identification
240 Ω to 360 Ω
Intended use
3.86 kΩ to 6.2 kΩ
Essential
characteristics
> 20 kΩ
Manufacturer
Contact information
For contact information, see www.utcfssecurityproducts.eu.
CS: Návod k instalaci
Popis
Zónový monitor IU2055C poskytuje rozhraní pro konvenční
hlásiče a kompatibilní adresovatelné ústředny EPS.
Modul slouží k monitorování konvenční zóny tj. detekci zkratu,
rozpojeného obvodu a poplachu.
Standard installation
IS installation
Standard installation
IS installation
0786
360-4109-0399
09
IU2055C
See DoP point 3
See DoP point 9
Gulf Security Technology Co.,Ltd
80, Changjiang East Road,
QETDZ, Qinhuangdao,
Hebei Province, China 066004
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
18 to 39 VDC
< 15 mA
< 35 mA
4.5 mA
1 µF
< 100 Ω
< 50 Ω
3 9 kΩ, 5%, 1/4W
5.6 kΩ, 5%, 1/4W
−5 to +40°C
−20 to +60ºC
10 to 95%
175 × 124 × 51 mm
325 g