Install the 1609 UPS in the Appropriate Environment
Do not operate the UPS where there is excessive dust or the temperature or
humidity are outside the specified limits
Mount the UPS
This unit is designed to mount on a heavy duty DIN rail or on the back panel of an
enclosure.
If mounted in an enclosure use six screws appropriate for the weight of the unit and
the mounting surface material.
Hardwire the UPS
Wiring of the UPS should be performed by a qualified electrician using appropriate wire gauges.
Start UP
Connect Power and Equipment to the UPS
1. The UPS features a transient voltage surge-suppression (TVSS) screw
for connecting the ground lead on surge suppression devices.
Prior to connecting the grounding cable, ensure that the UPS is NOT connected to input (utility), or battery power.
2. Wire the UPS.
3. Add optional accessories to the Network Management Card (NMC) slot.
4. Turn on all connected equipment. To use the UPS as a master on/off switch, be sure all connected equipment is switched on.
Standard Connectors
Contact Closure Port
The relays are connected from the common (COM) to the normally closed (NC) pins.When the unit enters a low battery or on battery
state, the appropriate relay will change state and connect the common (COM) to the normally open (NO) pin.
Output Contact Ratings:
Parameter
nominal switching capacity
maximum switching power
maximum switching voltage
maximum switching current
maximum carrying current
surge ratings
SERIAL PORT
Start the UPS
Press the
button on the front panel to start the UPS.
The battery charges to 90% capacity during the first four hours of normal operation. Do not expect full battery run capability during this
initial charge period.
Value
1 A @ 30 VDC
30 W
60 VDC
2 ADC
2 ADC
2 kV per Bellcore TA-NWT-001089
1.5 kV per FCC part 68
A special serial interface cable is included with the UPS. Because the pinout is unique, an off the
shelf cable will not be compatible with the UPS. This port enables remote configuration and
monitoring with the use of PowerChute
Use the cable supplied by APC.
located on the front panel. The TVSS screw is used
The emergency power off (EPO) feature is
user configurable. EPO provides immediate,
Contact Closure Port
remote de-energizing of connected
(located on front panel)
equipment without the device switching to
battery operation.
8 NO
ON
7 COM
BATTERY
The EPO interface is a Safety Extra Low
6 NC
5 NO
Voltage (SELV) circuit. Use a normally open
LOW
4 COM
SELV circuit to activate the EPO.
BATTERY
3 NC
2 EPO COM
1 EPO
®
Software.