Note:
All other PBX communication is interrupted when the
DACT sends event information via a PBX channel. For
increased security and to avoid such interruptions, we
recommend using a dedicated line for fire system event
communications.
Declaring EN 54-21 compliance
Declaration of EN 54-21 compliance for alarm transmission
and fault warning routing equipment is mandatory. When the
DACT is installed and configured, tick the EN 54-21 check box
on the label located on the underneath of the control panel
door.
Installing the GPRS board
The GPRS board is not included with the DACT board and only
limited installation information is included here. Refer to the
installation sheet included with the product for detailed
functional and technical specifications.
To install the GPRS board:
1.
Install the GPRS board onto the DACT board.
Use the plastic spacers provided and push the GPRS
board firmly onto the GPRS connector of the DACT board
(Figure 1, item 3).
2.
Check that the DIP switch settings match those described
in "DIP switch settings" below.
3.
Insert the SIM card into the SIM socket.
4.
Connect the antenna to the GPRS board.
5.
Restore the control panel power and test the GPRS signal
strength as described in "Testing" below.
6.
Configure the GPRS and CMS settings at the control
panel. See your control panel installation manual for
further information.
DIP switch settings
Set the DIP switch on the GPRS board as shown below.
MI_0
MI_1
BOOT
OFF
OFF
OFF
Testing
To test the DACT or GPRS:
1.
Select Test from the Main menu, and then select DACT
test.
2.
Select CMS.
A test message is sent to all configured CMS accounts
and the test result is displayed on-screen.
3.
Press F2 (Exit) to end the test and exit the menu.
Note:
Make sure that the DACT, GPRS (if applicable), and
CMS account information is configured at the control panel
before performing this test.
To test the GPRS signal strength:
1.
Select Test from the Main menu, and then select DACT
test.
2 / 32
HiLo
Test
ON
OFF
2.
Select GPRS.
The GPRS signal strength is displayed on the control
panel LCD.
No signal is indicated as −111 dBm. A good signal is in the
range −60 to 0 dBm (with the signal improving closer to
0 dBm).
3.
Adjust the antenna position to improve the signal strength,
if required.
4.
Press F2 (Exit) to end the test and exit the menu.
Specifications
Telephone lines
Cable type
Communication protocol
Operating voltage
Current consumption
Standby/activated
With GPRS board [2]
LED indications
Transmission (TX)
Receive (RX)
Operating environment
Operating temperature
Storage temperature
Relative humidity
Weight
Dimensions (W × H)
[1] Supplied by the control panel.
[2] Not included with the DACT board.
Compatibility
This product has been tested for compatibility with the
receivers listed in the table below.
Manufacturer
Receiver
Osborne-Hoffman
OH2000E
Sur-Gard
SG System I
Compatibility with other receivers using the Ademco Contact ID
protocol cannot be guaranteed.

Regulatory information

Certification
Manufacturer
UTC CCS Manufacturing Polska Sp. Z o.o.
Ul. Kolejowa 24, 39-100 Ropczyce, Poland.
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands.
13
Year of first CE
marking
EN 54
EN 54-21 [1]
P/N 501-407700-1-21 • REV 02.10 • ISS 19NOV13
2 max. (primary, backup)
Two-wire telephone cable with RJ-11
jack (or regional equivalent)
Contact ID
24 VDC [1]
45 mA at 24 VDC
100 mA max.
1 green LED
1 green LED
−5 to +40 °C
−20 to +50°C
10 to 95% (noncondensing)
40 g
110 × 52 mm