TIVAL Sensors
Telefon (0202) 75 94 08-0
Telefax (0202) 75 94 08-19
FF 4
For use in industrial and commercial applications as air compressors, water
pumps, booster pumps, fire-fighting equipment, oil supply equipment, high
pressure cleaning apparatus.
Observe regulations for installation and operation of electrical equipment.
!
Safety instructions:
Read installation instructions thoroughly. Failure to comply can result in
device failure, system damage or personal injury.
Installation should only be performed by persons having the appropriate
knowledge and skill.
Do not exceed specified maximum ratings for voltage, current, pressure
and temperature.
Protect against pulsations and liquid surges.
Avoid extreme vibrations.
Fix cable with stress-relief device.
Mounting:
• Fit pressure switch using the bracket on the bottom of the unit.
• Do not seal plastic pressure connector threads - use O-ring instead
Mounting location:
• Fit pressure switch at any angle as desired.
Setting per Fig. 2:
• Set upper switching-pressure with of adjusting screw 2. Pointer 3 will indicate.
• Set lower switching pressure by means of adjusting screw 4 -
upper switching pressure remains unchanged. Pointer 5 will indicate.
• Scales are not calibrated. Use manometer for
Wiring:
• Standard versions: Use figure 1
Reset:
• Standard version (FF 4-.. DAH): Automatic reset after pressure decrease below
lower switch point
• Version with manual reset (FF 4-.. DRH or DDH): Pressure decrease below
upper or increase above lower switchpoint and reset button 1 (per Fig. 2)
depressed.
Document Nr.: FF4F_65125_0714701_R03.doc
TIVAL Sensors GmbH
Am Brögel 19a
D-42285 Wuppertal
Germany
www.tival-sensors.com
Fig. 1
Fig. 2
setting.
precise
Replaces FF4F_65125_0714701_R02.doc
Operating Instructions
Pressure Control FF 4
Technical Data
Protection class per IEC 529 with rubber grummed
Protection class per IEC 529 with cable cland PG 13.5 / M20
Operating temperature TS, plastic press. connector
Operating temperature TS, all other press. connector
Resistance to vibration (10 ... 1000 Hz)
Electrical rating
Heating load (AC1; 230V AC)
Inductive load (AC15; 230V AC)
Inductive load (DC13; 230V DC)
Motor rating, full load (FLA)
Motor rating, locked rotor (LRA)
Type code FF 4-a b cde
a = Pressure range (bar)
2 = 0.11 ... 2
4 = 0.22 ... 4
8 = 0.5 ... 8
10 = 0.7 ... 10
12 = 1 ... 12
16 = 1 ... 16
30 = 3 ... 30
32 = 2 ... 32
60 = 8 ... 60
120 = 16 ... 120
250 = 30 ... 250
b = Version:
blank = standard version
c = diaphragm code
= D: perbunan
= A: stainless steel
= V: Viton
= P: plastic plunger
d = Reset code
= A: Automatic reset
= D: man. reset min.
= R: man. reset max
= M: Non standard version
e = Pressure connection
= H: G 3/8" female, silumin, DIN ISO 228/I
= Y: G 3/8" female, polyamid, DIN ISO 228/I
= G: G 1/4" female, steel, DIN ISO 228/I
= I: G 1/2" female, zinc die casting, DIN ISO 228/I
= F:1/4"-18 NPTF, ANSI B 1.20.3-1976
Standards
• VDE 0660, IEC 947-5-1, EN 60947-5-1
• Low Voltage Directive LVD 73/23/EWG; 93/68/EWG;
EN 60947-1; EN 60947-5-1: all models
• UL/CSA: FF444...
• Released for fire fighting equipment: FF 4-2 VdS, FF 4-2 VdS DRI,
FF 4-10 VdS, FF 4-16 VdS.
marking for all devices per Low Voltage Directive
• DIN 32733 / EN 12263, Pressure Equipment Directive PED 97/23/EC,
Category IV: for FF 4-12 AAG and FF 4-30 AAG only.
0035 marking for FF 4-12 AAG and FF 4-30 AAG.
19.07.2006
GB
IP 54
IP 65
0 ... +50°C
-20 ... +70°C
4g
16 A
6 A
0.1 A
10 A
60 A
PS (bar)
PT (bar)
20
40
24
40
30
40
32
40
12
16
36
48
30
42
52
64
100
120
200
240
400
500
VdS = VdS released version
PCN 0 714 701

Publicidad

loading

Resumen de contenidos para TIVAL FF 4

  • Página 1 • UL/CSA: FF444… • Version with manual reset (FF 4-.. DRH or DDH): Pressure decrease below • Released for fire fighting equipment: FF 4-2 VdS, FF 4-2 VdS DRI, upper or increase above lower switchpoint and reset button 1 (per Fig. 2) FF 4-10 VdS, FF 4-16 VdS.
  • Página 2 EN 60947-1; EN 60947-5-1: alle Modelle Elektrischer Anschluß: • UL/CSA: FF 4-… psi… , FF444… • Standard Ausführungen: Siehe Fig. 1 • Zulassung für Feuerlöschanlagen: FF 4-2 VdS, FF 4-2 VdS DRI, FF 4-10 VdS, Rückstellung: FF 4-16 VdS. • Standardausführung 4-..
  • Página 3: Montaje

    Rearme: • UL/CSA: FF444… • Versión Standard (FF4..DAH): Se rearma automáticamente cuando la presión • Aprobado para plantas anti-fuego: FF 4-2 VdS, FF 4-2 VdS DRI, FF 4-10 VdS, cae por debajo del punto de ajuste. FF 4-16 VdS. • Versión con rearme manual (FF4-..DRH o DDH): Cuando la presión se restablece dentro de los márgenes de ajuste se puede rearmar mediante el botón...
  • Página 4 (point bas) • Homologué pour la protection incendie: FF 4-2 VdS, FF 4-2 VdS DRI, • Version avec réarm. manuel (FF 4-.. DRH ou DDH) : Appuyer le bouton 1 FF 4-10 VdS, FF 4-16 VdS. (fig.2) pour réarmer lorsque la pression a dépasser le seuil bas ou haut suivant le modèle...
  • Página 5: Istruzioni Operative

    Allacciamento elettrico: • UL/CSA: FF444… • Esecuzione standard - vedi fig. 1. • Omologazione per impianti antincendio ad acqua: FF 4-2 VdS, Reinserzione: FF 4-2 VdS DRI, FF 4-10 VdS, FF 4-16 VdS. • Esecuzione standard (FF4-..DAH); reinserzione automatica in caso di caduta di •...
  • Página 6 • Het instelskala in niet geijkt. Voor een meer nauwkeurige instelling gelieve EN 60947-1; EN 60947-5-1: alle uitvoeringen een manometer te hanteren. • UL/CSA: FF444… • Goedkeuring voor blus installaties: FF 4-2 VdS, FF 4-2 VdS DRI, Elektrische aansluiting: FF 4-10 VdS, FF 4-16 VdS. • Standaard uitvoering: zie fig. 1 Reset: •...