Installation site selection - Indoor unit
AVOID
• Direct sunlight.
• Nearby heat sources that may affect unit performance.
• Areas where leakage of flammable gas may be expected.
• Locations where large amounts of oil mist may occur (such as
in kitchen or near fa c t o ry equipment) because oil contamination
can cause operation problems and may defo rm plastic surfa c e s
and parts of the unit.
• Unsteady locations that will cause noise or possible wa t e r
leakage.
• Locations where the remote control unit will be splashed with
water or affected by dampness or humidity.
• To make holes in areas where electrical wiring or conduits are
located.
DO
• Select an appropriate position from which every corner of the
room can be uniformily cooled.
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
D e ox i d i zed annealed copper tube for refri g e rant tubing connecting the units of the system; it has to be insulated with foamed polye t hy l e n e
(min. thickness 8mm).
MODEL
MA 7X - 9X
MA 12X - 18X
MA 2 2 X
PVC pipe for condensate drain pipe (ø int.18mm) in length suitable to connect the condensation to the outside dra i n a g e.
A n t i - f r e e ze oil for flare connections (about 30g.).
Multipolar electric wire with sufficient length to connect the units. S i ze and length of suggested electric wire are showed on table "Electri c a l
d a t a " . The wires have not to be lighter than mod. H07RN-F ( according to CEI 20-19 CENELEC HD22).

ELECTRICAL DATA

MODEL
Cross section area (mm
2
)
GR 7X
GR 9X
GR 12X
GR 18X
GR 22X
* 3-phase version
TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
MODEL
MA 7X - 9X
MA 12X - 18X
MA 22X
* If total tubing length becomes a) 10 to 15m, b) 10 to 30m (max.), charge additional refri g e rant (R22) by a) 15; by b) 25g/m.
No additional charge of compressor oil is necessary.
NARROW TUBE
OUTER DIAMETER
6,35 mm
6,35 mm
6,35 mm
LENGTH, SIZE WIRES AND DELAYED FUSE
Power supply wiring length
("A") m
2,5
77
41
34
22
100*
16
87*
MAX. ALLOWABLE
TUBING LENGTH AT
SHIPMENT
(m)
10
10
10
• Select a sufficiently strong location to support the weight of the
unit.
• Select a location where tubing and drain hose have the short e s t
run to the outside.
• A l l ow access for operation and maintenance as well as
unrestricted air flow around the unit.
Installation site selection - Outdoor unit
AVOID
• Heat sources, exhaust fans.
• Direct sunlight.
• Damp, humid or uneven locations.
• To make holes in areas where electrical wiring or conduits are
located.
DO
• Choose places as cool as possible and well ventilated.
• use lug bolts or equal to bolt down the unit, reducing vibration
and noise.
MIN. THICKNESS
0,8 mm
0,8 mm
0,8 mm
Power line length
("B") m
2,5
20 m
30 m
H
LIMIT OF TUBING
LENGTH
(m)
15
20
30
LARGE TUBE
OUTER DIAMETER
9,52 mm
12,7 mm
15,88 mm
Control line length
("C") m
1
20 m
30 m
H
LIMIT OF ELEVATION
DIFFERENCE
H
(m)
7
7
7
MIN. THICKNESS
0,8 mm
0,8 mm
1 mm
Delayed fuse
10A
20A
10A
20A
10A
REQUIRED AMOUNT OF
ADDITIOONAL
REFRIGERANT
(g / m)*
a) 15
b) 25
b) 25
(go on page 4)