Hi-lume Premier 0.1% EcoSystem / 3-wire Voltage LED Driver
Compatible Controls
Compatible Controls
• 3-Wire Controls
• EcoSystem Controls
Consult individual component installation guides for more
details.
Driver Leads
Maximum wire length between LED driver and start of the light engine:
Wire Gauge*
Maximum Lead Length
24 AWG (0.20 mm
2
)*
6 ft (1.8 m)
22 AWG (0.75 mm
2
)*
10 ft (3.0 m)
2
20 AWG (0.50 mm
)
15 ft (4.5 m)
18 AWG (0.75 mm
2
)
25 ft (7.62 m)
2
16 AWG (1.0 mm
)
40 ft (12.2 m)
14 AWG (1.5 mm
2
)
60 ft (18.3 m)
2
12 AWG (2.5 mm
)
100 ft (30.5 m)
10 AWG (4.0 mm
2
)*
150 ft (45.7 m)
* To use wire gauges larger or smaller than terminal blocks' rated gauge of
20 AWG to 12 AWG (0.50 mm
2
to 2.50 mm
2
), connect 12 in (30 cm) or less of
rated wire from terminal and connect with larger or smaller wire.
Field Adjustment Knob
Adjusting knob on the outside of the enclosure
changes the minimum light level that is reached during
normal operation. This feature enables the user to
address light output mismatch between two or more
drivers at low-end dim level. Driver is initially defaulted
to the minimum light output when at low-end. For more
information, please refer to Application Note #591
(P/N 048591) at www.lutron.com
1. Ensure knobs on all drivers are in the full counter-
clockwise position.
2. Set control to get lowest light level.
3. Turn knob clockwise to adjust light output to match the
brightest driver.
4. Repeat steps 2-3 for the remaining drivers.
Warranty
For warranty information, please visit: www.lutron.com/DriverWarranty
)Lutron, Lutron, Hi-lume, and EcoSystem are trademarks of Lutron Electronics Co., Inc.
registered in the U.S. and other countries.
©2015 – 2018 Lutron Electronics Co., Inc.
Compatible Controls
For assistance in selecting controls, contact our LED Center of Excellence.
For a complete list of compatible controls, see
www.lutron.com/hilumepremiervoltagecontrols
o m
r 0 .1 %
lu tr o n .c
P r e m ie
H i- lu m e
TM
-U
6 W 2 4 V
L 3 D 0 -9
er
LE D D riv
to -B la ck
TM
V ol ta ge
, F ad e-
on st an t
S o ft -o n
3- w ire C
D E L
n o ir
te m
nt e po ur
E co S ys
fo n d u au
TM
n co ns ta
e d o u x,
fil te ns io
A llu m ag
77 .7 66 1)
P ilo te 3-
(1 .8 44 .5
te m
T R O N 1
E co S ys
TM
1. 84 4. LU
an ad a:
U S A / C
M ax
11 0 W
- 0, 40 A
nt ré e:
H z 0, 92
In pu t | E
50 / 60
7 V ~
12 0 - 27
:
| S or tie
This device complies with part 15 of the FCC Rules. Operation is subject to the
C la ss 2
O ut pu t
4 A M ax
following two conditions:
24 ,0 V
t K no b
or tie
dj us tm en
se de S
(1) This device may not cause harmful interference
ut pu t A
m ité B as
Li gh t O
ur l'E xt ré
Lo w E nd
(2) This device must accept any interference received, including interference that may
la ge po
de R ég
B ou to n
cause undesired operation.
iè re
de Lu m
277 V~ NOTE: This equipment has been tested at 277 V~ and found to comply with
on ly .
en t.
the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits
G w ire
se ul em
- 12 A W
5 m m ²
U se 20
0, 50 - 2,
are designed to provide reasonable protection against harmful interference when the
un fil de
U til is er
rra te d
equipment is operated in a commercial environment. This equipment generates, uses,
llin g, se
ée s
s, de nt el
re ad -ro
e de fil et
x 3/ 8" th
and can radiate radio frequency energy and, if not installed and used in accordance
8" ro ul ag
w s: 8- 32
Li d sc re
8- 32 x 3/
uv er cl e:
with the instruction manual, may cause harmful interference to radio communications.
Vi s du co
Operation of this equipment in a residential area is likely to cause harmful interference
ns .
p lo ca tio
m id es .
fo r da m
en ts hu
Su ita bl e
in which case the user will be required to correct the interference at their own expense.
pl ac em
t au x em
C on vi en
m ov ed .
rt.
es t ou ve
ve r is re
120 V~ NOTE: This equipment has been tested at 120 V~ and found to comply with
in té rie ur
as tic co
in ne r pl
as tiq ue
y vo id if
er cl e pl
the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These
W ar ra nt
si le co uv
an nu lé e
or de at h.
G ar an tie
us in ju ry
limits are designed to provide reasonable protection against harmful interference in a
lt in se rio
M ay re su
lin g.
ha za rd .
or in st al
de gr av
es
residential installation. This equipment generates, uses and can radiate radio
: Sh oc k
se rv ici ng
ca us er
nc te ur
W AR NI NG
r be fo re
n. Pe ut
du di sjo
ct po we
tro cu tio
en ta tio n
frequency energy and, if not installed and used in accordance with the instructions,
Di sc on ne
er d' él ec
er l'a lim
tio n.
T : Da ng
ne . Co up
l'in st al la
tie n de
SS EM EN
la pe rs on
à l'e nt re
may cause harmful interference to radio communications. However, there is no
AV ER TI
cè s de
ou le dé
ta ge ou
au m on
lé sio ns
pr oc éd er
guarantee that interference will not occur in a particular installation. If this equipment
av an t de
does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
— Reorient or relocate the receiving antenna.
— Increase the separation between the equipment and receiver.
— Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
— Consult the dealer or an experienced radio/TV technician for help.
L3D0-96W24V-U Troubleshooting
Problem
Possible Solution
LED does not illuminate at
• Verify that the system is wired correctly according to wiring diagram and powered.
high-end
• Verify that the LED load is wired correctly; +LED to positive, -LED to negative.
• Verify that the LED load is for "constant-voltage" applications with PWM dimming.
• Verify that the LED load is compatible with the specified voltage output of the driver.
• Lutron drivers are not for use with MR16 LED lamps.
LED does not illuminate at
• Verify that the low-end trim on the control is set properly.
low-end
• Turn Field Adjustment Knob clockwise until desired low-end operation is obtained.
LED does not dim
• Verify that Switched Hot and Dimmed Hot are connected to the proper terminals
for 3-wire control.
• Verify EcoSystem control wiring (E1 and E2) is wired according to the instructions
for digital control.
LED turns on / off abruptly
• Turn Field Adjustment Knob counter-clockwise until desired low-end operation is
without Soft-on, Fade-to-
obtained.
Black feature
• 3-wire control does not have Soft-on, Fade-to-Black dimming technology.
LED is flashing, flickering,
• Verify that a compatible dimmer is being used to control the driver.
dropping out, or has poor
• Verify that the input voltage is within the rated limits.
dimming performance
• Verify that Switched Hot and Dimmed Hot are connected to the proper terminals.
• Verify that the LED load is for "constant-voltage" with PWM dimming applications.
• Verify that the length of wires between driver and LED does not exceed
specification.
• Verify that the rated voltage is present at the driver.
• Certain types of LED loads may be incompatible.* Verify that the LED load is within
the specified wattage range of 2 W to 96 W.
• Lutron drivers are not for use with MR16 LED lamps.
LED is flashing slowly (6 to
• Verify that the LED load does not exceed the maximum specified power rating of
8 second interval)
the driver (96 W).
• Verify that the LED load matches the specified voltage output of the driver.
• Verify that the length of wire between driver and LED does not exceed
specification.
• Certain types of LED loads may be incompatible.
LED output appears dim at
• Verify that rated line voltage is present at the terminal.
high-end
• Verify that the driver is operating in an environment within its ambient temperature
rating.
• Verify that the driver is not located adjacent to other heat producing devices. Verify
that space between drivers is greater than 3 in (76 mm).
• Verify that the maximum lead length is not exceeded per Lutron recommendation.
• Verify that the LED load is installed per manufacturer's instructions.
• Verify that the LED load is compatible with the specified voltage output of the driver.
Not all LED strips/fixtures
• Verify that multiple LEDs connected to a single driver are properly wired.
illuminate
• Verify that the LED load is installed per manufacturer's instructions.
Not all LEDs on the same
• Verify that the length of wire between the driver and LED does not exceed
strip are evenly lit
specifications.
• Verify that the LED load is for "constant-voltage" with PWM dimming applications.
• Verify that the LED load is installed per manufacturer's instructions.
LED is brighter / hotter than
• Verify that the LED load is compatible with the specified voltage output of the driver.
expected
* Certain constant-voltage loads may have added capacitance. Contact the Lutron LED Center of Excellence at 1.877.346.5338 or
LEDs@lutron.com for more information about these loads.
*