Compressor Defender™ Maintenance:
¡ AC Voltage SPD:
• Periodically check Compressor Defender™ to ensure green indicator LED is ON. If green LED
is OFF, protection has diminished and the Compressor Defender™ should be replaced immediately.
Table 1. LED Indicators (Diagnostics)
Condition
Surge Protected
No Surge Protection
Under Voltage
Short Cycle Protect
Unit Power Lost
Table 2. Operation
See operation table below for an overview of the Compressor Defender™ Operation
Condition
Under Voltage
Short Cycle Delay
Normally Closed Operation
Contactor Wiring
24 VAC
Compressor Contactor
Figure 4. 24 VAC Contractor Wiring.
Green LED
ON
OFF
−
Flash
OFF
Description
If line voltage falls below the accepted level, the relay output will open
until the line voltage returns to the accepted level. Voltage Drop Protection
conditions comply with AHRI standard 110-2012 Range B. For Voltage
conditions that drop below outside the limits of Range B prompt corrective
action is recommended
•
120 VAC Nominal – Range B 104 VAC
•
208 VAC Nominal – Range B 180 VAC
•
240 VAC Nominal – Range B 208 VAC
Once the line voltage exceeds the pick-up line voltage, the relay will close
after the time delay elapses. Delay = 3 Minutes (non-adjustable).
If surge or voltage monitoring protection is lost, the unit will continue nor-
mal compressor and thermostat operation without surge protection. The
unit should be replaced to restore surge protection to the circuit.
From Compressor
Defender™
Y1
C
Red LED
−
−
Flash
−
OFF
3