NSTALLATION INSTRUCTIONS – furniture feed only
Follow installation instructions from Concrete floor
installation.
1. Type S1R6FFxx factory assembled furniture feeds are shipped
with closure plugs (m) and (n) for the ¾" and 2" openings.
Openings must always be plugged when not in use.
installation requires closure plugs apply Teflon® tape or sealant
onto threads and tighten into threaded hole. Type S1R6FFxx
factory assembled furniture feeds is supplied with (2) metallic
screw-in connector fittings, (p) and (r). If installation requires
connector fittings apply Teflon® tape or sealant onto threads
and tighten into threaded hole.
2. A maximum of (10) #10 AWG type THHN (T-90 NYLON in
Canada) conductors may be fed through the ¾" opening side
of the service fitting.
3. A maximum of (30) Category 6 data cables (#23 AWG, 8
conductors, 4 twisted pair cable) may be fed through the 2"
opening side. When conductors larger than #22 AWG are
used, the aggregate cross sectional area must not exceed
the maximum of (30) Category 6 data cables (#23 AWG, 8
conductors, 4 twisted pair cable).
4. Remove the installation plate (j) and black spacer (o) and
retain the screws.
5. Feed wires through ¾" opening side and through tube (s).
6. Insert intumescent material sheet into interior of the can
assembly and around the tube (s).
7. Use the provided floor gasket (v) or apply a ¼ [6.3mm] thick
continuous bead of electrical type of RTV silicon sealant
compound fully around the perimeter on the underside of the
flange (w).
8. Attach Furniture Feed Cover flange (w) to the service fitting
(x). Align the tube (s) with smaller hole in bottom of the can.
Fasten cover (y) to feed cover flange (w) with three oval
screws (z) provided.
9. Attach ¾" and/or 2" liquid tight nonmetallic conduit (af) as
required to metallic screw in connectors. Nonmetallic conduit
is required to maintain the fire rating of the poke through
installation.
PD2462
(Page 2)
07/14
ABANDONMENT PLATE INSTALLATION INSTRUCTIONS
(Purchased separately):
S1R6ADMTxx abandonment plates provide an approved
method of abandoning the Hubbell S1R6PTxx series fire rated
poke through. This product will maintain the fire rating of the
poke through installation.
If
1. Disconnect power and/or telephone/data of the poke through.
2. Remove cover assembly by removing screws (ax) attaching
cover to the can. See Figure 11.
3. Install black spacer (o) and abandonment plate item (ag).
Coat supplied screws with sealant compound to ensure water
tightness before installing. Coat cover perimeter to ensure
water tightness.