SGE-3G/GPRS MODEM ROUTER
1.-DESCRIPTION
The SGE-3G/GPRS is a device that enables
connecting an application locally or to networks
using Internet IP protocols.
The
SGE-3G/GPRS
can
connect
networks (Universal Mobile Telecommunication
System) if the technology is available in the place it
is going to be installed. Otherwise, it can connect
via GPRS (General Packet Radio Service) as long
as the provider of the installed SIM card has
activated
the
services
required.
3G/GPRS is DYNDNS compatible for installations
that may not have a fixed IP.
It has 3 fully independent communications ports:
Ethernet, RS-232 and RS-485. If the RS-232 is not
being used, it can be used for sending SMS (Short
Message Service).
This manual can be found on CIRCUTOR's web site:
www.circutor.es
Disconnect the unit from all power supply sources
before undertaking any form of maintenance,
modification of connections, repairs, etc. Remove
the unit from service if any operational faults in the unit or its
protection elements are suspected.
If the unit is used in a different manner or outside the
manufacturer's specified limits, its protection elements may be
compromised and user's safety may be at risk.
2.-INSTALLATION
Bear in mind that when the unit is connected, the
terminals may have voltage and so touching them
may be dangerous. Likewise, opening covers or
removing safety elements may expose parts that are dangerous
to touch while the unit is powered. Do not use the unit until it is
fully installed.
The unit must be connected to a power circuit that is
protected with gl (IEC 269) or M type fuses with a
rating of 0.5 to 2 A. It must be fitted with a circuit
breaker or equivalent device in order to be able to
disconnect the unit from the power supply mains.
The unit's power circuit must be connected with a
cable that has a minimum cross-section of 1.5mm².
Placement of the DIN rail
fixing elements on the rear
Shows one of the options
of the unit. Remember to
for mounting the PANEL
raise the guides to make
base attachment guides.
sure they are correctly
The modules are
fastened once the guides
somewhat symmetrical,
are in place and the SGE-
and so can be attached to
3G/GPRS is correctly
the panel in various ways.
attached to the DIN rail.
One of the options for
mounting the PANEL on the
base attachment guides.
to
UMTS
2.1.-TERMINALS
The
SGE-
3.-START-UP
The
whole
configuration is done on the modem router web site,
so no additional software is needed for start-up.
However, a computer with an Ethernet port and a
crossover type network cable is necessary for
configuring the unit. The concentrator's default IP is:
IP: 192.168.1.1
Netmask: 255.255.255.0
The secure web protocol (HTTPS) must be used to
access the unit from the web site
Accessing with the browser: https://192.168.1.1
4.-OPERATION
4.1.-LED STATUS INDICATORS
The SGE-3G/GPRS has 11 LED that indicate the operating
status of the SGE-3G/GPRS. Meaning:
H
Very good coverage
M
Good coverage
L
Low coverage
Fixed: the unit is connected to the 3G networks
3G
Flashing: connected to GPRS networks
Stat
Flashing o Fixed: indicates the modem is active
Pmon Concentrator power supply
Indicates whether the concentrator is sending
TX
data (RS-232 or RS-485)
Indicates whether the concentrator is receiving
RX
data (RS-232 or RS-485)
How to insert the screws
for fastening the PANEL
to base attachment
elements.
How to insert the plastic
clips to fasten the
modules. This point is
very important, since the
purpose of the clips is to
ensure that the modules
are firmly secured.
:
10/100 Base-T (RJ45);
Ethernet
Ethernet IEEE802; 10/100 Mbits/s self-
adjusting
RS-232 Jack RJ11, without HW/SW
handshake
RS-485 Power strip: A (-), S(GND),
B(+)
Power Supply:Power strip
SGE-3G/GPRS
Modem
Router
The SIM card is located on
the back of the unit. Press
the button on the groove to
extract the card support.
SGE-3G/GPRS Modem router
ON
Flashing indicates the unit is operating correctly
4.2.-COMMUNICATIONS
4.2.a.- Ethernet Port
This communication port is used for communicating
with the PC or any other device connected to it. This
port can be used to configure the SGE-3G/GPRS
(on the web site).
4.2.b.- RS-232 Port
The unit is configured on the web site.
If the RS-232 port is deactivated, SMS messages
can be sent to the telephone number that has to be
configured on the unit's web site by bridging pins 4
and 5 for at least 3 seconds.
4.2.c.- RS-485 Port
This port is configured on the unit's web site.
5.-TECHNICAL FEATURES
Power circuit (AC)
Rated voltage
85 ...264 Vac
Power
7-12 VA
Frequency
50...60 Hz
Battery
Type
CR2032 SLF (ref 6032 201 501 VARTA)
Service life
5 years
Clock
Type
RTC maintained with battery.
Operating conditions
Operating temperature -10 ... +50 ⁰C
5 ... 95 %(without
Relative humidity
condensation)
Maximum altitude
2000 m
Protection degree
IP 41
Radio
Quadband
GSM/GPRS/EDGE:
Connection
GSM850/900/1800/1900
Dual band HSPA:900/2100
Transmission
GPRS
D/L up to 85.6 Kbps, U/L up to 85.6 Kbps
EDGE
D/L up to 236.8 Kbps, U/L up to 236.8 Kbps
UMTS
D/L up to 384 Kbps, U/L up to 384 Kbps
HSPA
D/L up to 7.2 Mbps, U/L up to 5.76 Mbps
Nominal impedance: 50 Ohms;
Antenna
SMA connector
Mechanical features
Dimensions
173x125x48
Safety
/
Category III – 300 Vac / class 2
Insulation
Standards
CE, IEC 60664, VDE 0110, UL 94, EN61010-1,
EN55011, EN61000-4-2, EN61000-4-3, EN61000-4-
11, EN 61000-6-4, EN 61000-6-2, EN 61000-6-1,
EN61000-6-3, EN61000-4-5.
EN301489-1,
EN301489-7,
EN301511, EN301908-1, EN301908-2.
6.-MAINTENANCE AND TECHNICAL SERVICE
Please contact our technical service for any
questions regarding operating the unit or
malfunctions
AFTER-SALES SERVICE
telephone: 902449459 (Spain)
+34 937452919 (outside Spain)
E-mail: sat@circutor.es
CIRCUTOR SA
Vial Sant Jordi, s/n
08232 Viladecavalls (Barcelona –Spain)
Email:central@circutor.es
(+34) 937 452 900, Fax (+34) 937 452 914:
M98249301-20-15A
EN301489-24,